The Schneider Electric Acti9 iCV40 A9DE6610 is a combined residual current circuit breaker with overcurrent protection RCBO 1P+N, 10 A, C curve and 300 mA type AC sensitivity. It integrates in a single compact device both magnetothermal protection against overloads and short circuits and residual current protection against earth leakage currents, simplifying the design and assembly of electrical panels.
Reference A9DE6610 features one protected pole plus neutral, with the neutral on the left side, and operates at a rated voltage of 230 V AC, 50/60 Hz. Its rated breaking capacity reaches 4.5 kA according to EN/IEC 61009-2-1.
The Acti9 iCV40 combines two protection functions within the same device. The thermal-magnetic trip unit protects the circuit against prolonged overloads and short circuits, while the residual current function monitors earth leakage currents.
This design makes it possible, in certain configurations, to replace the combination of a separate MCB and a residual current device, reducing the number of devices required inside the panel.
The Schneider Electric A9DE6610 has a rated current of 10 A and a C tripping curve. The magnetic operating threshold is between 5 and 10 times the rated current, a common characteristic for circuits with moderate inrush currents.
The residual current function has a 300 mA sensitivity and belongs to class AC. It is designed to detect sinusoidal alternating residual currents and trips instantly when the corresponding threshold is exceeded.
The 300 mA sensitivity is especially suitable for protection against insulation faults, indirect contact and fire risks associated with leakage currents, according to the design and requirements of each installation.
When regulations or circuit characteristics require additional high-sensitivity residual current protection, the appropriate sensitivity should be selected, such as 30 mA.
The A9DE6610 has a rated breaking capacity Icn of 4,500 A at 230 V according to EN/IEC 61009-2-1. Its service breaking capacity Ics also reaches 100% of Icn under the conditions specified by Schneider Electric.
The residual current tripping technology of the Acti9 iCV40 is voltage independent. In this way, the residual current function can operate in the event of a leakage current without relying on auxiliary electronic power supply to perform disconnection.
The Schneider Electric A9DE6610 is designed to be suitable for isolation and disconnection according to EN/IEC 61009-2-1, allowing the protected circuit to be electrically isolated during maintenance operations carried out in accordance with the relevant safety procedures.
The device is designed for clip-on installation on a DIN rail. Its slim format occupies only two module widths, allowing magnetothermal and residual current protection to be integrated without using the space required by two separate devices.
This design is especially useful in electrical panels where available space is limited.
The terminals accept conductors of different cross-sections depending on the type of cable used:
The device also features terminal design intended to facilitate wiring and identification of connections inside the electrical panel.
The Acti9 iCV40 A9DE6610 has a rated insulation voltage Ui of 400 V and a rated impulse withstand voltage Uimp of 4 kV.
The device offers an IP20 degree of protection and is intended for installation inside suitable electrical enclosures or panels. Its operating ambient temperature ranges from -5 to 60 °C.
The power loss indicated for this reference is approximately 2.9 W.
The Schneider Electric Acti9 iCV40 A9DE6610 provides in a single device 10 A C-curve magnetothermal protection and 300 mA type AC residual current protection. Its 1P+N configuration, 4.5 kA breaking capacity and compact DIN rail design make it a practical solution for protecting circuits against overloads, short circuits and leakage currents in residential and commercial electrical panels.