The Schneider Electric Acti9 ID K A9Z05425 residual current circuit breaker is a 4-pole, 25 A, 30 mA type AC RCCB designed to detect earth leakage currents and quickly disconnect the circuit when a differential fault occurs. Its instantaneous operation, front test button, and modular DIN rail mounting make it a practical solution for electrical panels in residential and commercial installations.
The A9Z05425 reference belongs to Schneider Electric’s Acti9 range and features four poles, with the neutral on the left. It operates at a rated voltage of 380-415 V AC and a frequency of 50/60 Hz, making it suitable for three-phase circuits with neutral within its electrical specifications.
The Schneider Electric ID K A9Z05425 has a 4-pole configuration and a rated current of 25 A. Its design enables simultaneous disconnection of the conductors associated with the circuit when a residual current above the set threshold is detected.
The A9Z05425 incorporates a 30 mA residual current sensitivity. This sensitivity level allows it to detect small earth leakage currents and provides residual current protection in electrical installations under the conditions established by applicable regulations.
Operation is instantaneous, with no intentional time delay, so the device opens the circuit when it detects a residual current that reaches the specified tripping conditions.
This model uses type AC residual current protection, designed to detect sinusoidal alternating residual currents. It is intended for circuits and loads compatible with this type of residual current protection.
The selection between type AC, type A, or other classes should be made taking into account the characteristics of the connected loads and the regulatory requirements of each installation.
The Acti9 ID K monitors the current balance between the active conductors of the circuit. When an earth leakage occurs and the residual current reaches the device’s operating level, the RCCB trips and opens the circuit.
Schneider Electric specifies this device for protection against electric shock by direct or indirect contact within the conditions defined for the product, while also helping reduce risks associated with insulation faults.
The front includes a test button that allows periodic checking of the correct operation of the residual current mechanism. This feature makes preventive maintenance tasks easier.
Schneider Electric recommends using the test button in accordance with the maintenance and safety instructions applicable to the device and the electrical installation.
The position of the lever allows the status of the residual current circuit breaker to be visually checked. In the event of tripping due to an earth leakage, the position of the handle makes it easy to identify the device status directly from the front of the panel.
This indication simplifies inspection and troubleshooting when a circuit disconnects.
The Schneider Electric A9Z05425 has a making and breaking capacity Im/Idm of 500 A. In addition, the manufacturer declares different conditional short-circuit current values when combined with compatible overcurrent protection devices.
Important: this product is an RCCB and does not provide built-in protection against overloads or short circuits. It must therefore be used together with the appropriate overcurrent protection devices for the installation.
The device has a rated insulation voltage Ui of 440 V AC and withstands impulse voltages up to 4 kV, features suitable for integration into low-voltage electrical panels.
The Schneider Electric Acti9 ID K A9Z05425 is designed for quick installation with clip-on DIN rail mounting. Its modular format makes it easy to integrate alongside miniature circuit breakers and other Acti9 components inside distribution boards.
The RCCB includes Bi-Connect terminals that allow conductors to be connected at the top or bottom. At the bottom, a compatible comb busbar can also be used, making electrical distribution inside the panel easier.
Schneider Electric specifies a mechanical durability of 5,000 cycles for this residual current circuit breaker. Its electrical durability reaches 2,000 cycles in AC-1 category.
The device offers an IP20 protection rating according to IEC 60529. Once correctly installed in a suitable modular enclosure, it can achieve protection of up to IP40.
The Schneider Electric A9Z05425 complies with the standards applicable to residual current circuit breakers without built-in overcurrent protection:
The Schneider Electric Acti9 ID K A9Z05425 provides high-sensitivity residual current protection for circuits up to 25 A, with 4 poles, 30 mA sensitivity, and instantaneous type AC operation. Its modular format, test button, Bi-Connect connection, and DIN rail mounting make it easy to integrate into residential and commercial electrical panels.
As an RCCB, it must be complemented by the appropriate miniature circuit breaker protection against overloads and short circuits, selected according to the characteristics of the installation.