The Schneider Electric Acti9 iID A9R35440 residual current circuit breaker is a four-pole RCD with 40 A rated current and 300 mA sensitivity, designed for three-phase electrical installations that require protection against earth leakage currents. This reference specifically corresponds to a selective, class A-SI superimmunized version, developed to improve service continuity and reduce unwanted tripping caused by certain electrical disturbances.
With a rated operational voltage of 380-415 V AC at 50/60 Hz, four poles and neutral on the left, the A9R35440 is part of the modular Acti9 iID range. Schneider Electric designs it to protect against indirect contact and the risk of fire resulting from insulation faults, while also providing circuit control and isolation functions.
The A9R35440 belongs to Schneider Electric’s A-SI category. Class A is designed to detect sinusoidal alternating residual currents and pulsating DC residual currents that may occur in installations with electronic equipment.
The SI, Super Immunized technology is developed to improve the performance of the residual current device in installations subject to electrical disturbances, reducing the risk of nuisance tripping that could unnecessarily interrupt the supply.
This feature is especially useful in panels with electronic loads, variable speed drives, power supplies, IT equipment, electronic lighting and other loads likely to generate network disturbances.
The A9R35440 has a selective time delay. This feature allows it to be coordinated with lower-sensitivity or instantaneous residual current devices installed downstream.
In a properly designed installation, selectivity helps ensure that in the event of a fault, the device closest to the fault operates first, avoiding disconnection of a larger part of the installation whenever possible.
Its 300 mA sensitivity is especially intended for protection against insulation faults and fire risk. It should not be confused with 30 mA residual current devices used as additional protection against certain electric shocks.
The residual current device incorporates four poles and is designed for three-phase installations with neutral. Schneider Electric places the neutral conductor on the left side of the device.
When a residual current trip or manual opening occurs, the device simultaneously interrupts all four poles, allowing the protected circuit to be isolated.
The rated current of the A9R35440 is 40 A. This value corresponds to the current the residual current device can carry under the conditions specified by Schneider Electric.
As an RCCB, its main function is to detect earth leakage. Protection against overloads and short circuits must be provided by an overcurrent protective device correctly coordinated with the residual current device.
Schneider Electric specifies a conditional short-circuit current of 10 kA. This value must be considered together with the short-circuit protective device installed upstream and the coordination conditions established by the manufacturer.
The rated making and breaking capacity Im is 1500 A, as is the differential making and breaking capacity Idm.
The A9R35440 is specified for a rated operational voltage of 380 to 415 V AC at 50/60 Hz, adapting to common low-voltage three-phase networks.
The rated insulation voltage is 500 V and the impulse withstand voltage reaches 6 kV, providing the dielectric characteristics required for use in distribution electrical panels.
The residual current detection mechanism uses voltage-independent tripping technology. This means the residual current function does not rely on an auxiliary electronic supply to trip when the corresponding residual current is reached.
Schneider Electric includes a red mechanical earth fault indication on the front. This signal helps distinguish a trip caused by leakage current from a manual opening of the switch.
The device also features a contact position indicator, making it easier to visually check the status of the residual current device during inspection and maintenance tasks.
The Acti9 iID A9R35440 is designed to be installed by clip-on mounting on a DIN rail. It occupies 8 x 9 mm pitches, equivalent to 4 modules of 18 mm.
Its modular format allows it to be combined with MCBs and other Acti9 devices inside residential, commercial and industrial distribution boards.
These dimensions correspond to four standard DIN modules and make integration into compatible modular enclosures easier.
The residual current device accepts top or bottom connections using simple terminals. Schneider Electric specifies the following conductor sizes:
The final conductor size must be selected taking into account circuit current, installation conditions and applicable electrical regulations.
Schneider Electric specifies a high service life for the Acti9 iID:
These performance levels make the device suitable for professional panels that require high reliability throughout their service life.
The A-SI version offers high immunity to certain transient disturbances. The technical documentation specifies a current impulse withstand of 3 kA with 8/20 µs wave.
This feature helps prevent unnecessary disconnections caused by brief disturbances that do not correspond to a permanent insulation fault.
The device has an IP20 protection rating according to IEC 60529. When installed in a suitable modular enclosure, it can achieve a higher front protection rating depending on the panel characteristics.
Schneider Electric specifies that this residual current device can be associated with a compatible ARA automatic reset device. For installations requiring automatic reset of a selective 4P 40 A 300 mA A-SI residual current device, the manufacturer provides for combination of the A9R35440 with the corresponding 3P/4P reset device.
The reset device is an independent accessory and is not included with the A9R35440 reference.
Due to its 300 mA sensitivity, selectivity and A-SI technology, this residual current device is especially suitable for:
The Schneider Electric Acti9 iID A9R35440 combines a 40 A rated current, 300 mA sensitivity, four poles and superimmunized, selective A-SI technology. This configuration makes it a particularly suitable solution for panels where residual current protection must be coordinated with downstream devices and nuisance tripping caused by electrical disturbances must be reduced.
Its 10 kA conditional short-circuit current, 500 V insulation voltage, DIN modular mounting and compatibility with Acti9 reset accessories make it easy to integrate into professional electrical installations. Residual current device selection and coordination should be carried out taking into account the protection architecture, required sensitivity and installation characteristics.