IDD Differential 4P 40A 300mA Class A with reference A9R35440 from the brand SCHNEIDER ELECTRIC
IDD Differential 4P 40A 300mA Class A with reference A9R35440 from the brand SCHNEIDER ELECTRIC
SCHNEIDER ELECTRIC

IDD Differential 4P 40A 300mA Class A

REF
A9R35440
(0)
Free shipping
292.00 €
€292.00
€1,382.88
Up to -7% for professionals. Discover it.
Schneider Electric Acti9 iID 4P 40A 300mA selective residual current circuit breaker, A-SI superimmunized class, 400V, 10kA conditional, for protection and isolation.
Buy now and receive it between 26 and November 30
Get +292 +584 Sumis for the purchase
Receive 2x Sumis for a limited time
More about the product

Information about IDD Differential 4P 40A 300mA Class A

The Schneider Electric Acti9 iID A9R35440 residual current circuit breaker is a four-pole RCD with 40 A rated current and 300 mA sensitivity, designed for three-phase electrical installations that require protection against earth leakage currents. This reference specifically corresponds to a selective, class A-SI superimmunized version, developed to improve service continuity and reduce unwanted tripping caused by certain electrical disturbances.

With a rated operational voltage of 380-415 V AC at 50/60 Hz, four poles and neutral on the left, the A9R35440 is part of the modular Acti9 iID range. Schneider Electric designs it to protect against indirect contact and the risk of fire resulting from insulation faults, while also providing circuit control and isolation functions.

Main features of the Schneider Electric A9R35440

  • Brand: Schneider Electric.
  • Range: Acti9.
  • Product: Acti9 iID.
  • Reference: A9R35440.
  • Type: RCCB residual current circuit breaker.
  • Number of poles: 4P.
  • Neutral position: left.
  • Rated current: 40 A.
  • Residual current sensitivity: 300 mA.
  • Residual current class: A-SI.
  • Superimmunized: yes.
  • Residual current time delay: selective.
  • Rated operational voltage: 380-415 V AC.
  • Frequency: 50/60 Hz.
  • Tripping technology: voltage independent.
  • Conditional short-circuit current: 10 kA.
  • Making and breaking capacity Im: 1500 A.
  • Differential making and breaking capacity Idm: 1500 A.
  • Insulation voltage Ui: 500 V.
  • Impulse withstand voltage Uimp: 6 kV.
  • Mounting: DIN rail.
  • Width: 72 mm.
  • Height: 91 mm.
  • Depth: 73.5 mm.
  • Weight: 0.37 kg.
  • Protection rating: IP20.
  • Standard: EN/IEC 61008-1.

Superimmunized A-SI class

The A9R35440 belongs to Schneider Electric’s A-SI category. Class A is designed to detect sinusoidal alternating residual currents and pulsating DC residual currents that may occur in installations with electronic equipment.

The SI, Super Immunized technology is developed to improve the performance of the residual current device in installations subject to electrical disturbances, reducing the risk of nuisance tripping that could unnecessarily interrupt the supply.

This feature is especially useful in panels with electronic loads, variable speed drives, power supplies, IT equipment, electronic lighting and other loads likely to generate network disturbances.

300 mA selective residual current device

The A9R35440 has a selective time delay. This feature allows it to be coordinated with lower-sensitivity or instantaneous residual current devices installed downstream.

In a properly designed installation, selectivity helps ensure that in the event of a fault, the device closest to the fault operates first, avoiding disconnection of a larger part of the installation whenever possible.

Its 300 mA sensitivity is especially intended for protection against insulation faults and fire risk. It should not be confused with 30 mA residual current devices used as additional protection against certain electric shocks.

4 poles for three-phase networks

The residual current device incorporates four poles and is designed for three-phase installations with neutral. Schneider Electric places the neutral conductor on the left side of the device.

When a residual current trip or manual opening occurs, the device simultaneously interrupts all four poles, allowing the protected circuit to be isolated.

40 A rated current

The rated current of the A9R35440 is 40 A. This value corresponds to the current the residual current device can carry under the conditions specified by Schneider Electric.

As an RCCB, its main function is to detect earth leakage. Protection against overloads and short circuits must be provided by an overcurrent protective device correctly coordinated with the residual current device.

10 kA conditional short-circuit current

Schneider Electric specifies a conditional short-circuit current of 10 kA. This value must be considered together with the short-circuit protective device installed upstream and the coordination conditions established by the manufacturer.

The rated making and breaking capacity Im is 1500 A, as is the differential making and breaking capacity Idm.

Operating voltage from 380 to 415 V

The A9R35440 is specified for a rated operational voltage of 380 to 415 V AC at 50/60 Hz, adapting to common low-voltage three-phase networks.

The rated insulation voltage is 500 V and the impulse withstand voltage reaches 6 kV, providing the dielectric characteristics required for use in distribution electrical panels.

Voltage-independent tripping

The residual current detection mechanism uses voltage-independent tripping technology. This means the residual current function does not rely on an auxiliary electronic supply to trip when the corresponding residual current is reached.

Earth fault trip indication

Schneider Electric includes a red mechanical earth fault indication on the front. This signal helps distinguish a trip caused by leakage current from a manual opening of the switch.

The device also features a contact position indicator, making it easier to visually check the status of the residual current device during inspection and maintenance tasks.

DIN rail mounting

The Acti9 iID A9R35440 is designed to be installed by clip-on mounting on a DIN rail. It occupies 8 x 9 mm pitches, equivalent to 4 modules of 18 mm.

Its modular format allows it to be combined with MCBs and other Acti9 devices inside residential, commercial and industrial distribution boards.

Compact dimensions

  • Width: 72 mm.
  • Height: 91 mm.
  • Depth: 73.5 mm.
  • Weight: approximately 0.37 kg.
  • Color: white.

These dimensions correspond to four standard DIN modules and make integration into compatible modular enclosures easier.

Conductor connection

The residual current device accepts top or bottom connections using simple terminals. Schneider Electric specifies the following conductor sizes:

  • Rigid conductor: 1 to 35 mm².
  • Flexible conductor: 1 to 25 mm².
  • Flexible conductor with ferrule: 1 to 25 mm².
  • Strip length: 14 mm.
  • Tightening torque: 3.5 Nm.

The final conductor size must be selected taking into account circuit current, installation conditions and applicable electrical regulations.

Mechanical and electrical durability

Schneider Electric specifies a high service life for the Acti9 iID:

  • Mechanical durability: up to 20,000 cycles.
  • Electrical durability: up to 15,000 cycles under the conditions indicated by the manufacturer.

These performance levels make the device suitable for professional panels that require high reliability throughout their service life.

Resistance to disturbances

The A-SI version offers high immunity to certain transient disturbances. The technical documentation specifies a current impulse withstand of 3 kA with 8/20 µs wave.

This feature helps prevent unnecessary disconnections caused by brief disturbances that do not correspond to a permanent insulation fault.

Protection rating and environmental conditions

The device has an IP20 protection rating according to IEC 60529. When installed in a suitable modular enclosure, it can achieve a higher front protection rating depending on the panel characteristics.

  • Operating temperature: -25 to 60 °C.
  • Storage temperature: -40 to 85 °C.
  • Pollution degree: 3.

Compatible with ARA automatic reset

Schneider Electric specifies that this residual current device can be associated with a compatible ARA automatic reset device. For installations requiring automatic reset of a selective 4P 40 A 300 mA A-SI residual current device, the manufacturer provides for combination of the A9R35440 with the corresponding 3P/4P reset device.

The reset device is an independent accessory and is not included with the A9R35440 reference.

Applications of the Schneider Electric A9R35440

Due to its 300 mA sensitivity, selectivity and A-SI technology, this residual current device is especially suitable for:

  • Main distribution boards.
  • Secondary boards with 30 mA residual current devices downstream.
  • Three-phase installations with electronic loads.
  • Commercial and industrial installations.
  • Retail premises and offices.
  • Installations with a risk of nuisance tripping.
  • Circuits where residual current selectivity is required.
  • Protection against insulation faults and fire risk.

Technical data of the Schneider Electric A9R35440

  • Manufacturer: Schneider Electric.
  • Range: Acti9.
  • Series: iID.
  • Reference: A9R35440.
  • Type: RCCB residual current circuit breaker.
  • Number of poles: 4P.
  • Neutral: left.
  • Rated current: 40 A.
  • Sensitivity: 300 mA.
  • Class: superimmunized A-SI.
  • Operating mode: selective.
  • Network type: AC.
  • Frequency: 50/60 Hz.
  • Rated operational voltage: 380-415 V AC.
  • Tripping technology: voltage independent.
  • Im: 1500 A.
  • Idm: 1500 A.
  • Conditional short-circuit current: 10 kA.
  • Ui: 500 V.
  • Uimp: 6 kV.
  • 8/20 µs impulse withstand: 3 kA.
  • Position indicator: yes.
  • Earth fault indicator: red mechanical.
  • Control: lever.
  • Mounting: DIN rail.
  • Modular width: 4 modules of 18 mm.
  • Width: 72 mm.
  • Height: 91 mm.
  • Depth: 73.5 mm.
  • Weight: approximately 0.37 kg.
  • Protection rating: IP20.
  • Mechanical durability: 20,000 cycles.
  • Electrical durability: 15,000 cycles.
  • Operating temperature: -25 to 60 °C.
  • Storage temperature: -40 to 85 °C.
  • Standard: EN/IEC 61008-1.

Selective A-SI residual current device to improve service continuity

The Schneider Electric Acti9 iID A9R35440 combines a 40 A rated current, 300 mA sensitivity, four poles and superimmunized, selective A-SI technology. This configuration makes it a particularly suitable solution for panels where residual current protection must be coordinated with downstream devices and nuisance tripping caused by electrical disturbances must be reduced.

Its 10 kA conditional short-circuit current, 500 V insulation voltage, DIN modular mounting and compatibility with Acti9 reset accessories make it easy to integrate into professional electrical installations. Residual current device selection and coordination should be carried out taking into account the protection architecture, required sensitivity and installation characteristics.

Specifications
Manufacturer
SCHNEIDER ELECTRIC
Reference
A9R35440
SKU
SCH65168049
Object
Differential
Number of poles
Assembly
Fixed
Nominal current
40 A
Network type
CA
Protection rating
IP20
Frequency
50/60 Hz
Datasheets
Reviews
Returns within 30 days
Shop with peace of mind. If something goes wrong, we'll take care of it.
After-sales service
Any questions? Our support team will be happy to help you.
Pay how and when you want
Card, bank transfer, PayPal... Installment? We have them all.
GroupSumi is your online distributor for construction, electrical material and climate control.
All rights reserved © 2026 GroupSumi