The Schneider Electric Acti9 iID A9R21225 residual current circuit breaker is a 2-pole, 25 A, 30 mA type A RCCB designed to detect earth leakage currents and disconnect the circuit instantly. It operates at a rated voltage of 220-240 V AC and features technologies such as VisiSafe and VisiTrip, which make it easier to check the device status and identify tripping events inside the electrical panel.
The A9R21225 reference belongs to Schneider Electric’s Acti9 iID range and is especially suitable for single-phase circuits where high-sensitivity residual current protection is required. As an RCCB residual current circuit breaker, it does not include overcurrent protection against overloads or short circuits, so it must be coordinated with the appropriate overcurrent protection device.
The Schneider Electric A9R21225 has a 2-pole configuration, with the neutral on the left, and a rated current of 25 A. It is designed for AC networks from 220 to 240 V and a frequency of 50/60 Hz.
The 30 mA residual current sensitivity allows the device to detect low-level residual currents and act quickly when an earth leakage occurs. This sensitivity is commonly used as additional protection against electric shock in installations where required by design and applicable regulations.
The residual current trip is instantaneous, with no intentional time delay.
The A9R21225 includes type A residual current protection. This class is designed to detect both sinusoidal alternating residual currents and pulsating direct residual currents, providing protection suited to many modern electrical and electronic loads.
This feature broadens the application range compared with a type AC RCD in circuits where pulsating residual current components may occur.
The Acti9 iID range incorporates VisiTrip, a front mechanical indication system that helps identify when the device has operated due to an earth leakage fault.
This signaling makes it easier to locate the affected circuit inside the panel and can reduce the time needed for troubleshooting and maintenance tasks.
VisiSafe technology provides a reliable indication of the open contact state, helping confirm circuit isolation before certain maintenance operations.
The device also includes a contact position indicator and is compatible with Acti9 padlocking accessories.
Schneider Electric specifies a rated residual making and breaking capacity of 1,500 A for the A9R21225.
The 10 kA rated conditional short-circuit current is achieved under the coordination conditions established by the manufacturer with the corresponding overcurrent protection device.
The residual current circuit breaker has a rated insulation voltage Ui of 500 V AC and withstands impulse voltages up to 6 kV, making it suitable for integration into low-voltage electrical panels.
The Schneider Electric Acti9 iID A9R21225 is designed for quick clip-on mounting on a DIN rail. Its 36 mm width corresponds to two standard 18 mm modules, making it easy to integrate into modular electrical panels.
The residual current device terminals allow connection from the top or bottom, offering flexibility during panel wiring. It also supports comb busbar distribution systems compatible with the Acti9 range.
The Schneider Electric A9R21225 is designed to provide a long service life in residential and commercial installations. The manufacturer specifies a mechanical durability of up to 20,000 cycles and an electrical durability of up to 15,000 cycles in AC-1.
The device has an IP20 protection rating according to IEC 60529. Once correctly installed in a suitable enclosure, it can achieve a protection rating of up to IP40.
The Acti9 iID A9R21225 complies with the standards applicable to residual current devices without built-in overcurrent protection:
The Schneider Electric Acti9 iID A9R21225 combines a 25 A rated current, 30 mA sensitivity and type A residual current protection in a modular format only 36 mm wide. Its ability to detect alternating and pulsating direct residual currents makes it a versatile solution for many modern electrical circuits.
The VisiTrip and VisiSafe technologies, high durability and DIN rail mounting make both installation and subsequent maintenance easier. As an RCCB, it must be complemented by the appropriate overcurrent protection against overloads and short circuits.