The Schneider Electric GV3P40 is a 3-pole thermal-magnetic motor circuit breaker from the TeSys Deca GV3 range, designed to protect three-phase motors against overloads and short circuits. It features a thermal adjustment range of 30 to 40 A, instantaneous magnetic protection, and phase-loss sensitivity. For motors at 400/415 V, it supports power ratings of up to 18.5 kW and offers an Icu breaking capacity of 50 kA, providing a compact solution for control panels and motor starters.
The GV3P40 includes rotary handle operation and EverLink power connections, developed to maintain a reliable electrical connection even under thermal variations and mechanical stress. It can be mounted on a rail or plate and combined with Schneider Electric TeSys Deca contactors to configure complete motor control and protection solutions.
The GV3P40 combines adjustable thermal protection and instantaneous magnetic protection in a single device. The thermal protection allows the motor circuit breaker to be set between 30 and 40 A to match the rated current of the protected motor.
In the event of a sustained overload, the thermal mechanism opens the circuit to prevent excessive motor heating. In the event of a short circuit, the magnetic protection acts quickly to limit the effects of high-intensity currents.
The magnetic trip current specified by Schneider Electric for this reference is 560 A.
The Schneider Electric GV3P40 incorporates phase-loss sensitivity in accordance with IEC 60947-4-1. This function is especially important in three-phase motors, since operation with one phase missing can cause severe current imbalance and overheating of the windings.
The motor circuit breaker therefore helps protect the motor not only against overloads and short circuits, but also against certain abnormal conditions associated with three-phase supply.
The maximum motor power that can be protected depends on the supply voltage. Schneider Electric specifies the following reference power ratings for the GV3P40:
Supply voltage Motor power 400/415 V AC 18.5 kW 500 V AC 22 kW 690 V AC 37 kWThe final selection must always be made according to the motor rated current and starting characteristics, using the device’s 30 to 40 A adjustment range.
The GV3P40 provides high short-circuit interruption capability. At a supply voltage of 400/415 V AC, it offers a 50 kA ultimate breaking capacity Icu in accordance with IEC 60947-2.
Voltage Icu breaking capacity 230/240 V AC 100 kA 400/415 V AC 50 kA 440 V AC 50 kA 500 V AC 12 kA 690 V AC 6 kAThe service short-circuit breaking capacity Ics reaches 100% of Icu at 230/240 V, 400/415 V and 440 V, while at 500 V and 690 V it corresponds to 50% of Icu.
The motor circuit breaker incorporates power connections using Schneider Electric EverLink technology. This connection system is designed to maintain stable contact pressure on conductors and provide a durable connection in motor control applications.
The specified tightening torque for the power terminals is 5 Nm. Conductor sizes and termination method must be selected according to Schneider Electric installation instructions.
The GV3P40 features a front rotary handle that allows manual opening and closing of the circuit. The device is also suitable for isolation in accordance with IEC 60947-1.
This system allows the motor circuit breaker to be used both as a protection device and for manual isolation of the circuit during certain maintenance operations, always respecting the applicable safety procedures.
The Schneider Electric GV3P40 can be secured using clips or screws and supports installation on either a rail or a plate. It can be installed in horizontal or vertical position according to Schneider Electric’s specified conditions.
These options make it easy to integrate into electrical panels for machinery, automation, pumping, ventilation, and other professional motor control installations.
Schneider Electric specifies a mechanical durability of 50,000 cycles for the GV3P40. Electrical durability also reaches 50,000 cycles for AC-3 use at 415 V and rated current, within the conditions established by the manufacturer.
The GV3P40 can be combined with Schneider Electric TeSys Deca contactors to form complete motor starting and protection assemblies. Schneider Electric includes, among others, combinations with LC1D40A, LC1D50A and LC1D65A contactors in properly coordinated applications.
This solution brings together overload and short-circuit protection, isolation, and motor switching using components from the same TeSys family.
The Schneider Electric GV3P40 motor circuit breaker is intended for protecting three-phase motors with a rated current within the 30 to 40 A range. It can be used in many electrical panels and automation systems.
Important: the GV3P40 is a thermal-magnetic motor circuit breaker and not a residual current device. It provides protection against overloads and short circuits and is sensitive to phase loss, but it does not replace residual current protection intended to detect earth leakage currents.
The Schneider Electric GV3P40 is designed in accordance with the standards applicable to motor protection and control, including IEC 60947-2 and IEC 60947-4-1. The range also has multiple international certifications for industrial applications.
With its adjustable 30 to 40 A range, 3 poles, 50 kA breaking capacity at 400/415 V, thermal-magnetic protection and EverLink connections, the Schneider Electric TeSys GV3P40 is a robust solution for the protection and isolation of three-phase motors up to 18.5 kW at 400/415 V.