The Schneider Electric Quick Vigi iC60 A9Q14225 differential block is a residual current protection module with 2 poles, 25 A and 300 mA sensitivity, designed to be paired with compatible Acti9 iC60 circuit breakers. Its AC residual current class detects sinusoidal alternating residual currents, while its instantaneous tripping disconnects the assembly when earth leakage reaches the specified threshold.
This device is not a standalone miniature circuit breaker: it is installed together with a compatible iC60 to form an assembly that combines overload and short-circuit protection with residual current protection against earth leakage. Thanks to the Quick Vigi system, the electrical connection to the circuit breaker is made via a plug-in connection, simplifying installation inside the electrical panel.
The A9Q14225 has a 300 mA residual current sensitivity. When the assembly detects a difference between the current entering and returning through the circuit equal to or greater than the specified tripping level, the system causes the associated circuit breaker to open.
The 300 mA sensitivity is mainly used for protection against insulation faults, indirect contact within the intended protection architecture, and reducing the risk of fire caused by electrical leakage. It should not be confused with a 30 mA RCD intended to provide additional high-sensitivity protection in circuits where regulations require it.
This reference corresponds to type AC residual current protection. It is designed to detect sinusoidal alternating residual currents that appear suddenly or increase progressively.
The residual current class must be selected according to the connected loads. In circuits incorporating certain electronic devices capable of generating pulsating or direct residual components, an A, A-SI or another type suitable for the application may be required.
The Quick Vigi A9Q14225 is an instantaneous residual current block, with no intentional trip delay. When the differential current reaches the device’s operating conditions, the mechanism commands the opening of the associated circuit breaker.
As it does not incorporate selective delay, coordination with other upstream or downstream residual current devices should be assessed when the installation requires residual current selectivity.
Schneider Electric specifies for this block a voltage-independent residual current tripping technology. The residual current detection function does not depend on an auxiliary electronic supply to trip when a sufficient leakage current appears.
This feature helps maintain the residual current protection function within the installation conditions specified by the manufacturer.
One of the main features of this reference is the Quick Vigi system. The block is electrically connected to the compatible circuit breaker through a plug-in connection, reducing the number of manual connections required between both devices.
This architecture simplifies panel assembly and makes it possible to create combined protection while maintaining the modularity of the Acti9 range.
The A9Q14225 is designed to be paired with compatible Schneider Electric Acti9 iC60 circuit breakers. The manufacturer’s documentation also includes compatibility within certain Acti9 Reflex iC60 configurations.
The rated current of the block is 25 A, so the selected circuit breaker must comply with the combinations, number of poles and current ratings authorized by Schneider Electric.
The residual current block alone does not provide overload or short-circuit protection. These functions are provided by the iC60 circuit breaker with which it is combined.
The device includes a mechanical residual current trip indicator. This signaling makes it possible to visually identify that the opening of the assembly was caused by earth leakage, helping distinguish this event from other disconnection causes.
The indication facilitates diagnosis and maintenance tasks in panels with multiple protection circuits.
When correctly combined with the corresponding circuit breaker, the Vigi iC60 provides complete protection against different electrical faults:
The block is designed for AC networks at 50/60 Hz. Schneider Electric specifies a rated operational voltage of 230/400 V AC according to EN 61009-1 and up to 230/415 V AC according to IEC 61009-1.
The rated insulation voltage Ui is 500 V and the rated impulse withstand voltage Uimp reaches 6 kV.
The technical documentation for the range specifies a current impulse withstand of approximately 250 A with 8/20 µs wave for this AC variant. This characteristic defines its behavior against certain short-duration transient disturbances.
For installations especially exposed to electrical disturbances or with sensitive electronic loads, it may be advisable to consider higher-immunity versions, such as the A-SI variants available within the Schneider Electric range.
The A9Q14225 is installed by clip-on mounting on a DIN rail and occupies 3 modules of 9 mm, equivalent to a total width of 27 mm.
These dimensions apply only to the Vigi block. The total installed width will be greater once coupled to the corresponding iC60 circuit breaker.
Schneider Electric specifies compatibility with distribution blocks and comb busbars on the lower side, facilitating integration within correctly configured Acti9 modular panels.
The connection layout must follow the manufacturer’s diagrams to ensure proper coupling between the residual current block, the circuit breaker and the distribution system used.
The lower tunnel terminals accept different conductor cross-sections:
The final conductor cross-section must be determined according to design current, installation method, temperature, voltage drop and applicable electrical regulations.
The device has an IP20 protection rating. Installed inside a suitable modular enclosure, the assembly can achieve a higher front protection rating depending on the panel characteristics.
Schneider Electric specifies pollution degree 3 for the intended operating environmental conditions.
The residual current block is designed to operate within a wide temperature range:
These temperatures must be considered together with the operating conditions of the coupled iC60 circuit breaker and the complete electrical panel.
This residual current block is intended for electrical panels where it is necessary to add 300 mA residual current protection to a compatible Acti9 circuit breaker. Applications include:
The Schneider Electric Quick Vigi iC60 A9Q14225 adds instantaneous 300 mA class AC residual current protection to a compatible Acti9 iC60 circuit breaker. Its plug-in connection simplifies installation and makes it possible to obtain overcurrent and earth leakage protection in a single assembly.
With a rated current of 25 A, two poles, trip indicator, voltage-independent residual current technology and a compact 27 mm width, it is a solution aimed at professional installations requiring protection against insulation faults and fire risk.
The reference corresponds only to the Vigi residual current block. To obtain complete overcurrent protection, it must be paired with a compatible Schneider Electric iC60 circuit breaker selected according to the current rating, number of poles, breaking capacity and installation characteristics.