The Schneider Electric Acti9 iID A9R61263 residual current circuit breaker is a 2-pole, 63 A, 30 mA sensitivity RCCB, designed to detect earth leakage currents and disconnect the circuit when the set threshold is exceeded. It features superimmunized type A-SI technology, instantaneous tripping, and voltage-independent residual current operation, offering greater immunity to transient disturbances that can cause nuisance tripping in conventional RCDs.
Reference A9R61263 belongs to Schneider Electric’s Acti9 iID range and is intended for single-phase networks of 220-240 V AC at 50/60 Hz. Its 30 mA sensitivity makes it suitable as a high-sensitivity residual current protection device in properly designed installations, while the A-SI class improves performance in circuits with electronic equipment, high-frequency disturbances, and pulsating residual currents.
The A9R61263 has a 2-pole configuration and a rated current of 63 A.
The rated current of 63 A indicates the current the device can carry under its operating conditions. The 30 mA sensitivity, on the other hand, corresponds to the residual current level at which the residual current protection operates.
The A-SI classification combines the detection characteristics of a type A RCD with Schneider Electric’s superimmunized technology.
A type A residual current device is designed to detect:
These leakage currents can occur in installations that include electronic equipment with rectifiers, power supplies, and other electronic components.
The SI technology provides greater immunity to certain transients and network disturbances, reducing the likelihood of unwanted disconnections when there is no real fault requiring circuit opening.
The Acti9 iID A-SI is especially suitable when the installation may be exposed to disturbances that make the operation of a conventional RCD more difficult.
It can offer advantages in installations with:
Suitability for a specific application should always be checked by taking into account the type of residual current that the load may generate.
Schneider Electric specifies a 3,000 A impulse current withstand with 8/20 µs wave for the A9R61263.
This feature is significantly higher than that of standard type A or AC residual current devices with lower immunity and helps prevent unnecessary tripping caused by certain transient phenomena.
The residual current tripping system is voltage-independent.
This means that the main residual current detection and tripping function does not rely on an auxiliary electronic supply to operate, within the conditions established by the applicable standards.
The main electrical supply characteristics are:
The residual current device has:
These values correspond to the device’s rated making and breaking capacity under standardized test conditions.
Schneider Electric specifies a conditional short-circuit current of 10 kA.
This value does not mean that the residual current device itself provides 10 kA thermal-magnetic protection. The conditional current is achieved when the RCCB is properly coordinated with the upstream short-circuit protective device.
The A9R61263 is a pure RCCB or residual current circuit breaker. Its function is to detect residual currents or earth leakage.
It does not include thermal-magnetic protection against overloads and short circuits. Therefore, it must be used together with miniature circuit breakers, fuses, or other correctly sized overcurrent protection devices.
It should not be confused with an RCBO, which combines thermal-magnetic and residual current protection in a single device.
The Schneider Electric Acti9 iID includes a red mechanical front indicator that makes it possible to identify an operation associated with a residual current fault.
This signaling facilitates diagnosis in panels containing numerous devices and allows certain trip conditions to be visually distinguished.
The device also features contact position indication, allowing the switch status to be checked visually.
This feature makes routine inspection, commissioning, and panel maintenance easier.
As a residual current circuit breaker, the Acti9 iID includes a test circuit and test button intended to periodically check the residual current tripping mechanism.
The test should be carried out following Schneider Electric’s instructions and the maintenance recommendations applicable to the installation.
Schneider Electric declares the A9R61263 suitable for isolation in accordance with:
This feature allows the device to be used as a circuit isolation element within the corresponding safety conditions and procedures.
The residual current device is designed for clip-on mounting on a DIN rail, making it easy to integrate with miniature circuit breakers and other Acti9 modular devices.
Its two-module format allows a 63 A two-pole residual current protection device to be installed in just 36 mm of panel width.
The terminal design allows connections from the top or bottom, providing flexibility in the internal layout of the panel.
The A9R61263 is designed to integrate into Acti9 panels and supports distribution systems using compatible comb busbars from the top or bottom, depending on the configuration of the assembly.
This makes it easier to build neat panels and reduces the number of individual cable links required between compatible devices.
The switch is compatible with the Acti9 padlocking device.
This option allows the operating handle to be mechanically locked when maintenance or safety procedures require preventing unauthorized operation.
Schneider Electric specifies:
These ratings make it suitable for professional installations subject to routine testing, switching, and disconnection operations.
The A9R61263 offers an IP20 protection rating as a modular device.
It must be installed inside a suitable enclosure or electrical panel that provides the required protection degree for the environmental conditions of the installation.
The type A-SI is especially interesting in installations where 30 mA sensitivity is required and electronic equipment may increase the risk of unwanted tripping.
When properly sized, it can be part of panels intended for:
The Schneider Electric Acti9 iID A9R61263 combines a 63 A rated current and 30 mA sensitivity with type A-SI technology, offering detection of alternating and pulsating direct residual currents together with greater immunity to certain electrical transients.
Its 3 kA impulse withstand, voltage-independent operation, red mechanical earth fault indicator, and compact two-module format make it a particularly interesting solution for panels with electronic loads where minimizing the risk of nuisance tripping is important.
Important: the A9R61263 is an RCCB residual current circuit breaker and not an MCB or RCBO. It does not protect against overloads or short circuits on its own, so it must be installed together with correctly sized overcurrent protection. The 10 kA conditional short-circuit current only applies with the appropriate associated protection.