The Schneider Electric TeSys GB2CD08 is a thermal-magnetic circuit breaker specifically designed for the protection of control and command circuits against overloads and short circuits. It features a 1P+N configuration, with one protected pole and the neutral disconnected simultaneously, a rated current of 3 A, and a magnetic trip current of 40 A.
This miniature circuit breaker belongs to Schneider Electric’s TeSys GB2 range and can operate on both AC and DC networks. It offers an Icu breaking capacity of 3 kA at 230/240 V AC in accordance with IEC 60947-2 and has an especially compact width of just 15 mm, designed to save space in automation and machinery electrical panels.
The GB2CD08 reference includes one thermally and magnetically protected pole plus one neutral pole that disconnects simultaneously. Therefore, although it physically interrupts two conductors, it should not be confused with a conventional two-pole circuit breaker with two protected poles or with a residual current device.
Its rated current of 3 A makes it especially suitable for low-power auxiliary and control circuits used in machinery and automation systems.
The TeSys GB2CD08 combines two protection systems:
Schneider Electric specifies a magnetic trip current of 40 A, approximately equivalent to 13 times the device’s rated current.
In accordance with IEC 60947-2, the GB2CD08 has a ultimate breaking capacity Icu of 3 kA at 230/240 V AC. The service breaking capacity Ics is 50% of Icu under these conditions.
This capacity is suited to its main function as a protection device for auxiliary and control circuits within machinery and automation electrical panels.
The Schneider Electric GB2CD08 can be used on AC and DC networks within the values specified by the manufacturer.
This compatibility makes it suitable for a wide variety of industrial auxiliary circuits.
The TeSys GB2 is mainly developed for the protection of control circuits. It can be used in electrical panels associated with machinery and automated installations to protect elements such as:
The GB2CD08 is designed for clip-on mounting on a 35 mm symmetrical DIN rail. It can also be installed on a compatible plate, providing flexibility during panel design.
Its width of only 15 mm makes it possible to make the most of available space and is especially useful in panels with a high density of control devices.
The circuit breaker accepts different conductor types and cross-sections through its connection terminals:
Schneider Electric specifies a mechanical durability of 8,000 cycles and an electrical durability of 8,000 cycles, offering performance suitable for professional control and automation applications.
The power loss indicated by the manufacturer is approximately 2 W per pole.
The TeSys GB2CD08 has an IP20 protection rating according to IEC 60529, so it is intended to be installed inside a panel or enclosure that provides the level of protection required by the installation.
The Schneider Electric GB2CD08 provides thermal and magnetic protection for 3 A auxiliary circuits while occupying only 15 mm of panel width. Its 1P+N configuration allows phase and neutral to be disconnected simultaneously, while maintaining thermal-magnetic protection on the phase conductor.
Its combination of 3 A, 40 A magnetic trip, 3 kA breaking capacity, AC/DC compatibility, and DIN rail mounting makes it an especially suitable solution for automation panels, machinery, and professional control circuits.
Important: the GB2CD08 does not provide residual current protection against earth leakage. For this function, a suitable residual current device must be installed according to the characteristics of the installation.