The Schneider Electric Acti9 Vigi C120 A9N18598 residual current block is a differential protection module with 4 poles, 125 A and 300 mA sensitivity, designed to be paired with compatible Acti9 C120 circuit breakers. This reference features superimmunized type A-SI protection and instantaneous operation, providing a solution especially suited to commercial, tertiary and industrial installations where protection against earth leakage is required with high immunity to electrical disturbances.
The Vigi C120 does not replace the thermal-magnetic circuit breaker: it is coupled to the C120 to complete its protection functions. The thermal-magnetic breaker provides protection against overloads and short circuits, while the Vigi module adds detection of residual differential currents. Together, they provide combined protection adapted to circuits up to 125 A.
The A9N18598 has a rated residual current sensitivity of 300 mA. The block monitors the current balance between the circuit conductors and trips the assembly when it detects an earth leakage that reaches the specified operating conditions.
Schneider Electric positions the 300 mA Vigi C120 versions among solutions intended for protection against indirect contact and for reducing the risk of fire caused by insulation faults.
A 300 mA sensitivity should not be confused with 30 mA devices used as additional personal protection in circuits where regulations require high sensitivity.
One of the most important features of this reference is its A-SI classification. Type A can detect both sinusoidal alternating residual currents and certain pulsating DC residual currents generated by electronic equipment.
The SI, Super Immunized technology developed by Schneider Electric increases the device's immunity to electromagnetic disturbances and certain transients that could cause nuisance tripping in a conventional residual current device.
This makes the A9N18598 especially suitable for installations incorporating power electronics, power supplies, IT equipment, electronic lighting, variable speed drives or other loads capable of generating disturbances on the network.
This Vigi C120 version operates instantaneously, without an intentional delay intended to achieve time selectivity.
When the residual current reaches the corresponding operating level, the module causes the associated circuit breaker to open. If the installation requires selective coordination with other residual current devices, the complete architecture must be assessed and, where appropriate, a specific selective version selected.
The A9N18598 has a 4-pole configuration, suitable for pairing with compatible four-pole C120 circuit breakers.
This configuration allows the conductors of the circuit to be monitored together in three-phase installations with neutral and to trip the associated breaker when an earth leakage current is detected.
Schneider Electric specifies a rated current of 125 A for this reference. The Vigi C120 range is specifically designed to complement C120 circuit breakers up to 125 A.
The selection of the block and the associated circuit breaker must comply with the pole count and current ratings authorized by the manufacturer.
The Vigi C120 A9N18598 is an adaptable residual current block. It is designed to work in combination with a compatible Acti9 C120 circuit breaker and not as an independent overcurrent protection device.
Once assembled, the assembly provides:
The electrical connection between the Vigi block and the circuit breaker is made by screws. Schneider Electric designs the range so that the compatible residual current block can be coupled to the corresponding C120, forming a single protection assembly.
The modular system simplifies the configuration of distribution boards and allows the circuit breaker and the required residual current sensitivity or class to be selected separately.
The A9N18598 uses voltage-independent residual current technology. The operation of the residual current function does not depend on an external auxiliary electronic supply to detect and trip in the event of an earth leakage.
This feature is covered by Schneider Electric within the performance of the Vigi C120 range in accordance with IEC/EN 61009-2-1.
The block is specified for a rated operational voltage of 230 to 415 V AC at 50 Hz, covering the usual voltages used in low-voltage three-phase distribution networks.
Its rated insulation voltage Ui is 500 V and the impulse withstand voltage Uimp reaches 6 kV.
The A-SI version is designed to offer greater service continuity in the face of disturbances that can cause unwanted tripping in other residual current devices. The technical documentation available for this reference specifies a 3 kA impulse current withstand.
This feature is especially relevant in installations subject to transient overvoltages, load switching or disturbances caused by electronic equipment.
The Vigi C120 range includes a front mechanical residual trip indication. This signaling makes it possible to visually identify that the opening of the assembly was caused by an earth leakage.
Quick identification of the cause of tripping facilitates maintenance and troubleshooting in boards with multiple circuits.
The Vigi C120 has a test button to periodically check the operation of the residual current mechanism.
The test must be carried out following Schneider Electric's instructions and the maintenance recommendations for the installation.
The assembly is designed to be clipped onto a 35 mm symmetrical DIN rail, making it easy to integrate into professional modular panels.
The product documentation indicates an occupation of 10 x 9 mm modules for the block in its configuration.
The Schneider Electric technical sheet for reference A9N18598 specifies the following overall dimensions:
These measurements must be considered together with the dimensions of the associated C120 circuit breaker when calculating the total space required in the panel.
The Vigi C120 uses tunnel terminals that allow the connection of large cross-section conductors, in line with its rated current of up to 125 A.
The final cross-section must be calculated according to the design current, installation method, temperature, voltage drop and applicable electrical regulations.
Schneider Electric specifies a mechanical durability of up to 20,000 cycles, providing a long service life within the conditions established for the product.
The device has an IP20 protection rating. It must be installed inside a panel or electrical enclosure that provides the level of protection required by the environmental conditions of the installation.
The specified pollution degree is 3 according to IEC 60947-2.
Thanks to its A-SI technology, the block is designed to operate over a wide temperature range:
Schneider Electric technical documentation specifies compliance with:
These standards govern devices incorporating residual current protection associated with overcurrent protection and the specific characteristics of the residual current function.
Due to its rated current, sensitivity and A-SI technology, the residual current block is suitable for applications such as:
The Schneider Electric A9N18598 allows you to add 300 mA residual current protection to a compatible Acti9 C120 circuit breaker, combining a 125 A rated current, four poles and superimmunized A-SI technology with instantaneous tripping.
Its high immunity to disturbances helps improve service continuity in installations with electronic loads, while type A detection broadens residual current protection compared with a conventional type AC solution.
This reference corresponds only to the Vigi C120 residual current block. To obtain complete protection against overloads, short circuits and earth leakage, it must be installed together with a compatible C120 circuit breaker correctly sized for the installation.