The Schneider Electric Acti9 Vigi C120 A9N18571 is a 4-pole, 125 A, 500 mA sensitivity additional residual current block, designed to be coupled with compatible Acti9 C120 miniature circuit breakers. It incorporates type AC residual current protection, instantaneous tripping and voltage-independent trip technology, allowing earth leakage detection to be added to the overload and short-circuit protection provided by the associated C120 MCB.
The A9N18571 reference is especially suited to distribution boards where four-pole residual current protection with a rated current of up to 125 A is required. It operates on 230 to 415 V AC networks at 50/60 Hz, has a residual current sensitivity of 500 mA, an insulation voltage Ui of 500 V and an impulse withstand voltage Uimp of 6 kV. It is important to note that this is an additional Vigi block and not a standalone circuit breaker: it must be installed together with a suitable C120 MCB.
The A9N18571 belongs to the Acti9 Vigi C120 family, specifically designed to add residual current protection to circuit breakers in the Acti9 C120 range.
Once correctly connected to the compatible C120 MCB, the assembly provides protection against overloads, short circuits and earth leakage currents.
The Vigi block has a rated residual current of 500 mA. When it detects a residual current reaching the set tripping conditions, it causes the associated circuit breaker to open.
A 500 mA sensitivity is mainly intended for indirect contact protection in properly designed systems and reducing the risk of fire associated with leakage currents.
It should not be confused with a 30 mA residual current device, which is commonly used as additional protection against direct contact in circuits where required by regulations. The sensitivity must be selected according to the earthing system, earth resistance, existing protections and applicable standards.
The A9N18571 belongs to class AC. This type of protection is intended to detect sinusoidal alternating residual currents.
Before selecting a type AC RCD, the nature of the connected loads should be checked. Electronic equipment capable of generating pulsating DC residual current components may require a type A RCD or another more suitable protection class.
This reference uses instantaneous residual current protection, meaning it does not include the intentional delay characteristic of selective models.
This feature must be taken into account when several levels of residual current protection are connected in cascade. If vertical selectivity between RCDs is required, the corresponding combination of sensitivities and delays should be studied.
Schneider Electric specifies voltage-independent residual current trip technology.
Residual current detection and mechanical tripping do not depend on an auxiliary electronic supply to perform their main function within the conditions specified by the manufacturer.
The Vigi C120 A9N18571 block is designed for a rated current of 125 A.
It must only be combined with a compatible and correctly selected C120 circuit breaker. The rated current of the assembly, conductor cross-section and circuit characteristics must be verified during installation design.
The main electrical characteristics of the residual current block are:
These ratings allow integration into three-phase distribution boards within the specified voltage and insulation conditions.
The Schneider Electric A9N18571 is specifically designed as an additional block for Acti9 C120 circuit breakers.
The electrical connection to the MCB is made by screws, and the system design facilitates the creation of a combined protection unit.
In the assembly:
By itself, the A9N18571 must not be used as an MCB or as a standalone overcurrent protection device.
The block is designed for clip-on installation on a 35 mm symmetrical DIN rail, making it easy to integrate into modular electrical panels.
The reference features tunnel terminals adapted to the current ratings of the C120 range.
Respecting the specified cross-section and tightening torque is essential to avoid overheating and ensure reliable electrical connection at high currents.
The Schneider Electric technical data sheet published for this reference indicates:
The dimensions should be considered together with the configuration of the associated C120 breaker when planning the available space in the panel.
The Vigi C120 has an IP20 protection rating.
As a modular component intended for electrical panels, it must be installed inside a suitable enclosure that provides the environmental protection level required by the installation.
Schneider Electric specifies a mechanical durability of 20,000 cycles, providing a long service life under the device's rated conditions.
The 500 mA sensitivity allows the device to be used as part of a system for protection against indirect contact, provided that the electrical and regulatory conditions corresponding to the earthing system used are met.
The effectiveness of this protection depends on parameters such as earth resistance, touch voltage limit, coordination with other devices and the maximum permitted disconnection times.
Schneider Electric also identifies the Vigi C120 range as a solution intended to help protect installations against the risk of fire caused by earth leakage currents.
Persistent leakage currents can generate heating at defective insulation points. The device detects this type of residual current and disconnects the circuit when the set threshold is reached.
The residual current block can be used in panels with compatible Acti9 C120 breakers in numerous professional applications:
The Schneider Electric Acti9 Vigi C120 A9N18571 adds 500 mA type AC instantaneous residual current protection to a compatible C120 circuit breaker, forming a protection assembly against earth leakage, overloads and short circuits.
Its 125 A rated capacity, four-pole configuration, voltage-independent residual current operation and connection for rigid conductors up to 50 mm² make it a solution aimed at high-current distribution boards.
Important: the A9N18571 is an additional residual current block and does not function as a standalone MCB protection device. It must be coupled to a compatible Acti9 C120. Likewise, its 500 mA sensitivity should not be considered equivalent to a 30 mA RCD for additional personal protection; the appropriate sensitivity must be selected according to the application and installation standards.