The Schneider Electric Acti9 C120N A9N18369 circuit breaker is a 3-pole, 125 A, C-curve protection device designed to protect electrical distribution circuits against overloads and short circuits. It incorporates a thermal-magnetic trip unit, is suitable for isolation, and can be installed on a 35 mm DIN rail, offering a robust solution for residential, commercial, and professional electrical panels.
The A9N18369 reference belongs to Schneider Electric’s Acti9 C120 range. It features a rated breaking capacity Icn of 10 kA at 230-400 V AC according to IEC/EN 60898-1 and an ultimate breaking capacity Icu of 10 kA at 380-415 V AC according to IEC/EN 60947-2. Its C curve provides magnetic tripping between 5 and 10 times the rated current, making it suitable for many distribution circuits with moderate inrush currents.
The Schneider Electric C120N A9N18369 has 3 protected poles and a rated current of 125 A at 30 °C. All three poles include thermal and magnetic protection and are operated together by a single front lever.
The C tripping curve is intended for circuits that may present moderate transient currents during energization. Schneider Electric specifies a magnetic threshold between 5 and 10 times the rated current.
This allows the A9N18369 to be used in many distribution applications, sub-distribution boards, and circuits supplying loads with some inrush current, provided that the curve and rating selected are compatible with the conductor cross-section, available short-circuit current, and load characteristics.
The thermal-magnetic mechanism combines two operating systems:
This combination allows the C120N to be used as an overcurrent protection device within low-voltage distribution boards.
According to IEC/EN 60898-1, the Schneider Electric A9N18369 offers a rated breaking capacity Icn of 10,000 A in 230 to 400 V AC networks at 50/60 Hz.
In applications evaluated according to IEC/EN 60947-2, the ultimate breaking capacity Icu depends on the operating voltage:
Therefore, the breaking capacity value must always be interpreted together with the operating voltage and the applicable standard.
Schneider Electric also specifies the following service breaking capacity values:
The Acti9 C120N A9N18369 is suitable for isolation according to IEC 60947-2. This feature allows it to be used as a circuit isolation device within the manufacturer’s specified operating conditions.
The range also includes contact position indication and VisiSafe technology, providing visual signaling to help confirm that the contacts are open before carrying out certain maintenance operations.
The circuit breaker has class 3 current limiting. Its ability to limit energy during a short circuit helps reduce thermal and electrodynamic stresses transmitted to downstream conductors and components.
The A9N18369 offers insulation characteristics suitable for professional electrical distribution panels:
Schneider Electric specifies different rated operating voltages depending on the network type and the standard considered:
The circuit breaker is designed for quick clip-on installation on a 35 mm symmetrical DIN rail. It can be integrated with other protection and control devices from the Acti9 family.
One of the advantages of the Acti9 C120 range is the possibility of complementing the circuit breaker with different auxiliary devices. Schneider Electric provides for the addition of signaling, tripping, and remote monitoring auxiliaries, as well as compatible Vigi residual current blocks.
This makes it possible to configure a system adapted to the protection, control, and monitoring needs of each electrical panel.
The A9N18369 uses tunnel terminals designed for large cross-section conductors, in line with its 125 A rated current.
The Schneider Electric C120N is designed to withstand a high number of operations over its service life.
The device has an IP20 protection rating according to IEC 60529, so it is intended to be installed inside a suitable electrical enclosure or panel.
The Acti9 C120 range is designed to operate in demanding environments and supports the following thermal conditions:
Due to its 125 A rating, the C120N has a larger format than conventional lower-current modular circuit breakers, while still allowing direct DIN rail installation.
Schneider Electric specifies an approximate total dissipation of 12.3 W for this reference, corresponding to about 4.1 W per pole. This value may be relevant when calculating the total thermal dissipation of panels with several power devices installed.
The Schneider Electric Acti9 C120N A9N18369 combines a high rated current of 125 A, three-pole protection, and a C curve with a breaking capacity suitable for professional distribution applications. Its thermal-magnetic design provides protection against overloads and short circuits in a single device.
The possibility of adding signaling and tripping auxiliaries, monitoring devices, and Vigi residual current blocks, together with its suitability for isolation, DIN rail mounting, and VisiSafe technology, makes it easy to integrate into complete electrical panels adapted to different protection and control needs.