The Schneider Electric A9N18372 is a thermal-magnetic circuit breaker from the Acti9 C120N range, designed to protect low-voltage electrical circuits against overloads and short circuits. It features 4 protected poles, a rated current of 80 A and C tripping curve, with a breaking capacity of 10 kA under the conditions specified by Schneider Electric. Its modular design allows it to be installed on DIN rail in residential, commercial and professional distribution boards.
The C120N combines thermal tripping for sustained overloads and instantaneous magnetic tripping in the event of short circuits. It is also suitable for isolation and can be complemented with electrical auxiliaries, remote monitoring devices and compatible Acti9 Vigi residual current blocks.
The Schneider Electric Acti9 C120N uses a thermal-magnetic tripping unit. The thermal element operates when a prolonged overcurrent occurs that could cause excessive heating of the conductors, while the magnetic trip responds quickly to high short-circuit currents.
This combination protects electrical lines against two of the main overcurrent faults that can occur in low-voltage installations.
Reference A9N18372 has four poles and thermal-magnetic protection on all four poles. This configuration allows simultaneous disconnection of the four connected conductors and is suitable for installations where a four-pole circuit breaker is required.
Its rated current is 80 A at a reference temperature of 30 °C, according to the technical data published by Schneider Electric.
The thermal-magnetic breaker uses a C curve, with a magnetic operating threshold between 5 and 10 times the rated current. This type of curve is widely used in distribution circuits that may present moderate inrush currents when certain loads are switched on.
The selection of the curve and rated current must take into account the characteristics of the installation, conductor cross-section, connected loads and the expected short-circuit current.
Schneider Electric specifies different breaking capacity values depending on the operating voltage and the applicable standard. For common distribution networks, the A9N18372 reaches a 10 kA breaking capacity.
Voltage Breaking capacity Standard 230-400 V AC 10 kA Icn IEC/EN 60898-1 220-240 V AC 20 kA Icu IEC/EN 60947-2 380-415 V AC 10 kA Icu IEC/EN 60947-2 440 V AC 6 kA Icu IEC/EN 60947-2In addition to the ultimate breaking capacity, the manufacturer specifies the service breaking capacity Ics for different voltages.
Voltage Ics 230-400 V AC 7.5 kA 220-240 V AC 15 kA 380-415 V AC 7.5 kA 440 V AC 4.5 kAThese values make it possible to assess the breaker’s ability to continue operating after interrupting a short-circuit current within the conditions established by the standard.
The Acti9 C120N has limitation class 3. This current-limiting capability helps reduce the energy passing through the circuit during a short circuit and therefore the thermal and electrodynamic stresses borne by downstream conductors and equipment.
The A9N18372 is declared suitable for isolation in accordance with IEC/EN 60947-2. This feature allows the device to be used to electrically isolate the circuit within the conditions established by the manufacturer.
The breaker also includes a contact position indicator that makes it easier to visually check its status during inspection and maintenance tasks.
The Schneider Electric C120N is designed for clip-on mounting on a symmetrical 35 mm DIN rail. This makes installation inside modular panels easier alongside other protection and control devices from the Acti9 range.
Schneider Electric also indicates compatibility with comb busbar systems, which helps simplify electrical distribution between several devices and reduce wiring time in compatible configurations.
The A9N18372 uses tunnel terminals prepared for large cross-section conductors, suitable for its 80 A rated current.
Conductor type Accepted cross-section Rigid conductor 1 to 50 mm² Flexible conductor 1.5 to 35 mm² Strip length 15 mm Tightening torque 3.5 NmSchneider Electric specifies a mechanical durability of 20,000 cycles and an electrical durability of 5,000 cycles for the C120N under the corresponding test conditions.
These performance figures make the device suitable for panels where robust protection and a high number of operations over its service life are required.
The Acti9 C120N platform allows different electrical auxiliaries and remote monitoring devices to be added to expand the breaker’s signalling, control and tripping functions.
Schneider Electric also provides the possibility of combining the C120N with a compatible Vigi residual current block when the installation requires earth leakage protection.
The A9N18372 on its own is a thermal-magnetic breaker and therefore does not include integrated residual current protection.
The Schneider Electric Acti9 C120N A9N18372 is mainly designed for high-current distribution circuits that require four-pole protection against overloads and short circuits.
The Schneider Electric A9N18372 thermal-magnetic breaker complies with EN/IEC 60898-1 and EN/IEC 60947-2, applicable to low-voltage circuit breakers for overcurrent protection.
The Schneider Electric A9N18372 Acti9 C120N combines four protected poles, 80 A rated current, C curve and 10 kA breaking capacity in a modular DIN rail format. Its thermal-magnetic protection, isolation capability and compatibility with Acti9 auxiliaries and Vigi blocks make it a versatile solution for high-current distribution boards.