Schneider Electric Acti9 C60H-DC 1P 16 A circuit breaker, C curve and 250 V DC. Protects direct current circuits against overloads and short circuits, with a 6 kA breaking capacity.
Buy now and receive it between 20 and November 23
Express delivery
Get +67 +133 Sumis for the purchase
Receive 2x Sumis for a limited time
More about the product

Information about C60H Circuit Breaker 250V 1P 16A Curve C

The Schneider Electric Acti9 C60H-DC A9N61511 miniature circuit breaker is a modular automatic switch specifically designed to protect DC circuits against overloads and short circuits. It features 1 protected pole, a rated current of 16 A, C tripping curve, and an operating voltage of up to 250 V DC, providing a compact solution for distribution, automation, control, and other DC-powered applications.

This circuit breaker uses a thermal-magnetic trip unit: thermal protection acts against sustained overloads, while magnetic tripping responds quickly to high short-circuit currents. At 250 V DC, it offers an Icu breaking capacity of 6 kA according to IEC/EN 60947-2.

DC-specific miniature circuit breaker

The A9N61511 belongs to the Acti9 C60H-DC family, developed by Schneider Electric for DC installations. The manufacturer explicitly states that these circuit breakers combine the functions of overload and short-circuit protection, control, and isolation.

Its rated operating voltage reaches 250 V DC in single-pole configuration, with an operating range from 24 to 250 V DC. Due to its polarized design, it is essential during installation to respect the polarity indicated on the front of the device. Incorrect polarity connection may compromise safety and the proper operation of the circuit breaker.

16 A and C tripping curve

The A9N61511 reference offers a rated current of 16 A at 25 °C and a C tripping characteristic. The magnetic trip threshold is approximately between 7 and 10 times the rated current, providing overcurrent protection and allowing use in different DC distribution circuits.

The thermal-magnetic technology combines in a single device protection against prolonged overloads and rapid action against short circuits, helping protect both conductors and downstream connected equipment.

High breaking capacity in DC

The breaking capacity of the C60H-DC varies depending on the installation voltage. According to IEC/EN 60947-2, Schneider Electric specifies an Icu breaking capacity of 20 kA at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC.

The service breaking capacity Ics corresponds to 75% of Icu. At 250 V DC, this means a service breaking capacity of 4.5 kA.

Suitable for isolation

In addition to its protection function, the Schneider Electric A9N61511 is suitable for isolation according to IEC/EN 60947-2. The positive contact indication allows the contact status to be visually checked via the front signaling of the device.

The quick-make mechanism is independent of the speed at which the handle is operated, while the rapid opening of the contacts helps limit current during a fault and reduce electrical stress on downstream equipment.

Modular DIN rail mounting

The C60H-DC is designed for fixed mounting on a 35 mm symmetrical DIN rail. With a width of only 18 mm, equivalent to a standard module, it makes efficient use of the available space inside the electrical panel.

Installation can be carried out in different positions. The device allows top or bottom feed, provided that Schneider Electric’s indicated polarity is strictly respected.

Connection and maintenance

The circuit breaker uses screw terminals for copper conductors. For ratings up to 25 A, Schneider Electric documentation specifies connections of up to 25 mm² with solid conductor and up to 16 mm² with flexible conductor, with a tightening torque of 2.5 Nm.

The device also supports compatible accessories and auxiliaries from the C60 family to add signaling or remote tripping functions depending on the installation configuration.

Technical characteristics of the Schneider Electric A9N61511

  • Brand: Schneider Electric.
  • Reference: A9N61511.
  • Range: Acti9.
  • Model: C60H-DC.
  • Type: modular thermal-magnetic circuit breaker.
  • Application: DC electrical distribution.
  • Number of poles: 1P.
  • Protected poles: 1.
  • Rated current: 16 A at 25 °C.
  • Network type: direct current.
  • Rated operating voltage: 250 V DC.
  • Operating voltage range: 24-250 V DC.
  • Tripping curve: C.
  • Tripping technology: thermal-magnetic.
  • Magnetic threshold: approximately 7-10 x In.
  • Icu breaking capacity at 110 V DC: 20 kA.
  • Icu breaking capacity at 220 V DC: 10 kA.
  • Icu breaking capacity at 250 V DC: 6 kA.
  • Service breaking capacity Ics: 75% of Icu.
  • Utilization category: A.
  • Suitable for isolation: yes.
  • Rated insulation voltage Ui: 500 V DC.
  • Impulse withstand voltage Uimp: 6 kV.
  • Mounting: 35 mm DIN rail.
  • Width: 18 mm.
  • Height: 85 mm.
  • Depth: approximately 73 mm.
  • Weight: approximately 0.128 kg.
  • Degree of protection: IP20 on the device and IP40 when installed in a suitable modular enclosure.
  • Solid conductor: up to 25 mm².
  • Flexible conductor: up to 16 mm².
  • Tightening torque: 2.5 Nm.
  • Mechanical durability: up to 20,000 cycles.
  • Electrical durability: 3,000 cycles with L/R of 2 ms and up to 6,000 cycles with resistive load.
  • Operating temperature: -25 to 70 °C.
  • Storage temperature: -40 to 85 °C.
  • Maximum operating altitude: 2,000 m.
  • Standard: IEC/EN 60947-2.
  • EAN: 3606480424120.

Applications of the Acti9 C60H-DC 1P 16 A

The Schneider Electric A9N61511 is suitable for DC distribution circuits used in automation, control systems, transportation, and other DC electrical installations. Its modular format makes it easy to integrate into both new panels and expansion or maintenance operations.

The combination of 16 A, C curve, 250 V DC, and 6 kA breaking capacity at maximum voltage makes the C60H-DC a suitable solution for protecting DC circuits against overloads and short circuits, while also providing control and isolation functions.

Important: this model is specific to direct current and must be connected respecting the polarity indicated on the front of the device.

Specifications
Manufacturer
SCHNEIDER ELECTRIC
Reference
A9N61511
SKU
SCH94681C37
Object
Automatic switch
Number of poles
1P
Assembly
Fixed on symmetrical DIN rail of 35 mm
Nominal current
16 A
Network type
CC
Protection rating
IP20
Color
White
Datasheets
Reviews
Returns within 30 days
Shop with peace of mind. If something goes wrong, we'll take care of it.
After-sales service
Any questions? Our support team will be happy to help you.
Pay how and when you want
Card, bank transfer, PayPal... Installment? We have them all.
GroupSumi is your online distributor for construction, electrical material and climate control.
All rights reserved © 2026 GroupSumi