The Schneider Electric Acti9 iC60H A9F89416 miniature circuit breaker is a modular automatic circuit breaker with 4 protected poles, 16 A and C curve, designed to protect electrical installations against overloads and short circuits. It stands out for its high breaking capacity, with 10 kA Icn at 400 V AC according to IEC/EN 60898-1 and 15 kA Icu at 380-415 V AC according to IEC/EN 60947-2. It incorporates VisiTrip and VisiSafe technologies, thermal-magnetic protection, energy limiting class 3 and suitability for isolation.
The A9F89416 reference belongs to Schneider Electric's Acti9 iC60H range, developed for circuits that require a higher breaking capacity than conventional modular miniature circuit breakers. Its four-pole configuration, DIN rail mounting and compatibility with auxiliaries, monitoring systems and Vigi residual current blocks make it easy to integrate into residential, commercial, tertiary and industrial electrical panels.
The Schneider Electric A9F89416 has 4 poles and 4 protected poles, so the thermal-magnetic protection acts on the four conductors connected to the device.
The Acti9 iC60H combines two operating principles:
In this way, the device protects conductors and the circuit against the main risks associated with overcurrents.
The A9F89416 reference uses a C tripping curve. Schneider Electric specifies a magnetic threshold of 8 × In ±20%.
The C curve offers a balance between fast short-circuit protection and tolerance to transient inrush currents, which is why it is commonly used in distribution circuits and loads with moderate starting peaks.
It can be used, provided the installation calculations allow it, in circuits such as:
According to IEC/EN 60898-1, the A9F89416 offers a rated breaking capacity Icn of 10,000 A at 400 V AC and 50/60 Hz.
Its service breaking capacity according to the same standard is:
This high breaking capacity makes the iC60H suitable for installations where the prospective short-circuit current exceeds the performance of lower-capacity modular ranges.
When evaluated according to IEC/EN 60947-2, Schneider Electric specifies different ultimate breaking capacity Icu values depending on voltage:
Therefore, the 10 kA and 15 kA values commercially associated with this product are both correct, but they correspond to different standards and test conditions.
According to IEC/EN 60947-2, the main Ics values are:
Before selecting the circuit breaker, it must be checked that its breaking capacity is suitable for the maximum prospective short-circuit current at the installation point.
The A9F89416 has energy limiting class 3 according to IEC/EN 60898-1.
This capability helps reduce the energy and peak current flowing through the circuit during a short circuit, lowering the thermal and electrodynamic stresses on conductors and downstream devices.
The VisiTrip system provides local indication that makes it easy to identify the breaker that has tripped due to a fault.
In panels with many circuits, this function helps quickly locate the affected outgoing circuit and can reduce the time needed to diagnose the issue.
The VisiSafe technology allows visual confirmation that the contacts are physically open through the corresponding device indication.
The circuit breaker is also suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2 and is suitable for industrial isolation according to IEC/EN 60947-2.
The iC60H range offers a higher breaking capacity than the equivalent iC60N range, making it especially interesting in panels where high short-circuit currents are expected.
This feature makes it suitable for professional and industrial distribution applications, provided the rest of the electrical parameters are appropriate for the circuit.
Schneider Electric specifies the iC60H A9F89416 for AC and DC applications within its rated conditions.
In DC, it has an Icu of 15 kA up to 250 V DC. In this type of installation, the connection diagrams, maximum voltage and pole configuration established by Schneider Electric must be strictly observed.
The A9F89416 is designed for fixed clip-on mounting on DIN rail, making it easy to integrate with other Acti9 modular devices.
Its four-module format allows high-breaking-capacity four-pole thermal-magnetic protection to be incorporated into standard modular electrical panels.
The terminals allow connection from the top or bottom of the device and accept compatible distribution combs.
Proper conductor preparation and tightening are essential to ensure a reliable connection and avoid abnormal heating at the terminals.
The iC60H can be complemented with different accessories from the Acti9 platform to expand the panel's protection and monitoring functions.
Schneider Electric allows the addition of:
Compatibility must always be checked with the specific accessory reference.
The A9F89416 is an MCB circuit breaker and provides protection against overloads and short circuits.
It does not include integrated residual current protection against earth leakage. When this function is required, it can be used together with suitable residual current protection or associated with a compatible Vigi block in accordance with Schneider Electric instructions.
This robustness makes it suitable for professional installations subject to regular switching, testing and maintenance operations.
The circuit breaker has an IP20 protection rating according to IEC 60529.
It must be installed inside a suitable enclosure or electrical panel that provides the environmental protection level required by the application.
Thanks to its 16 A rated current, C curve and high breaking capacity, this circuit breaker can be used in different distribution circuits provided electrical calculations confirm its suitability.
The Schneider Electric Acti9 iC60H A9F89416 combines four protected poles, 16 A and C curve with a high breaking capacity: 10 kA Icn at 400 V according to IEC/EN 60898-1 and 15 kA Icu at 380-415 V according to IEC/EN 60947-2.
Its VisiTrip and VisiSafe systems make fault location and maintenance operations easier, while compatibility with auxiliaries and Vigi blocks allows the device's functions to be expanded within the Acti9 platform.
Important: before installing the A9F89416, the design current, conductor cross-section, tripping curve, minimum and maximum short-circuit current and required breaking capacity must be checked. This device does not include residual current protection; when protection against earth leakage is required, it must be complemented with a suitable residual current device.