The Schneider Electric Acti9 iC60H A9F89206 miniature circuit breaker is a modular automatic circuit breaker with 2 protected poles, 6 A and C curve, designed to protect electrical circuits against overloads and short circuits. It stands out for its high breaking capacity, with an Icn breaking capacity of 10 kA at 400 V AC according to IEC/EN 60898-1 and an Icu of 15 kA at 380-415 V AC according to IEC/EN 60947-2. It incorporates VisiTrip and VisiSafe technologies, thermal-magnetic protection and suitability for isolation, offering a solution especially suitable for professional distribution boards where a higher breaking capacity than a conventional 6 kA miniature circuit breaker is required.
Reference A9F89206 belongs to Schneider Electric's Acti9 iC60H range. Its bipolar configuration allows both conductors connected to the device to be protected simultaneously, while its two-module format, DIN rail mounting and compatibility with auxiliaries and Vigi residual current blocks make it easy to integrate into residential, commercial, tertiary and industrial panels.
The Schneider Electric A9F89206 has 2 poles and 2 protected poles. Both conductors are protected by the thermal-magnetic tripping system and are disconnected simultaneously when the breaker trips.
The Acti9 iC60H combines two protection mechanisms:
This combination helps protect wiring and loads against the main risks associated with overcurrent.
The A9F89206 incorporates a C curve. Schneider Electric specifies a magnetic tripping threshold of 8 × In ±20 %.
This feature allows certain transient current peaks to be tolerated without immediate magnetic tripping, provided the installation has been correctly designed.
Depending on the specific circuit characteristics, the C curve can be used in applications such as:
According to IEC/EN 60898-1, the Schneider Electric A9F89206 has a rated breaking capacity Icn of 10,000 A at 400 V AC.
This value is one of the main differences between the iC60H and the lower breaking capacity iC60N versions.
The service breaking capacity according to the same standard is:
According to IEC/EN 60947-2, commonly used as a reference in professional and industrial applications, Schneider Electric specifies different ultimate breaking capacity Icu values depending on voltage:
Therefore, on a 400 V network, the 15 kA value corresponds to Icu according to IEC/EN 60947-2, while the 10 kA value corresponds to Icn according to IEC/EN 60898-1.
The main Ics values specified for the A9F89206 are:
The required breaking capacity must be selected according to the maximum short-circuit current expected at the installation point.
The Acti9 iC60H has energy limiting class 3 according to IEC/EN 60898-1.
During a short circuit, the limiting capability reduces peak current and the energy passing through the circuit before disconnection is completed, reducing the thermal and electrodynamic stresses on downstream cables and equipment.
The VisiTrip technology makes it easy to visually identify a miniature circuit breaker that has tripped due to an electrical fault.
This indication helps quickly identify the affected outgoing circuit in panels with many circuits, reducing the time needed to locate the issue.
The VisiSafe system provides a reliable indication of the open contact position and helps improve safety during maintenance and circuit isolation operations.
The A9F89206 is also declared suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2.
Schneider Electric expressly specifies suitability for industrial isolation according to IEC/EN 60947-2.
This feature allows the miniature circuit breaker to be integrated into professional installations where a device suitable for isolating the circuit during certain service and maintenance tasks is required.
The A9F89206 is specified for AC networks and certain DC applications.
In DC, Schneider Electric indicates an Icu breaking capacity of 15 kA up to 125 V DC.
When using the device in DC, the maximum voltage, configuration and connection conditions indicated by Schneider Electric must always be respected.
The main dielectric characteristics include:
The Schneider Electric A9F89206 is designed for fixed mounting on a DIN rail.
The modular format makes installation alongside other Acti9 protection, control and distribution devices easier.
Its 36 mm width corresponds to two standard panel modules.
The terminals allow connection from the top or bottom.
Correct terminal tightening is essential to prevent overheating and ensure a reliable electrical connection.
The A9F89206 supports supply via combs or busbars compatible from both the top and bottom.
This makes it easier to assemble multiple Acti9 devices in modular panels and reduces the number of individual cable jumpers.
The Acti9 platform allows the iC60H to be complemented with different compatible accessories.
These may include:
The exact compatibility must be checked using the accessory reference and Schneider Electric tables.
The A9F89206 is a miniature circuit breaker. Its function is to protect the circuit against overloads and short circuits.
It does not itself include residual current protection against earth leakage. When the installation requires residual current protection, it can be combined with a compatible solution, such as a suitable Vigi block, or installed together with a correctly selected residual current device.
Schneider Electric specifies:
These features are intended to provide a long service life when the device operates within its rated conditions.
The miniature circuit breaker has an IP20 protection rating according to IEC/EN 60529.
It is intended to be installed inside a panel or enclosure that provides the environmental protection level required by the installation.
Thanks to its 6 A rated current and high breaking capacity, it can be used in low-current circuits where bipolar protection with a higher interruption capacity is required.
Possible applications include:
The Schneider Electric Acti9 iC60H A9F89206 combines a 6 A rated current, two protected poles and C curve with a high breaking capacity of 10 kA at 400 V according to IEC/EN 60898-1 and 15 kA Icu at 380-415 V according to IEC/EN 60947-2. This makes it a suitable option for panels where the expected short-circuit level requires higher performance than lower-capacity ranges can offer.
VisiTrip and VisiSafe technologies, compatibility with Acti9 auxiliaries, the possibility of adding Vigi residual current protection and its two-module format make it easy to create compact and easily monitored protection systems.
Important: before installing the A9F89206, the circuit design current, conductor cross-section, C curve, minimum and maximum short-circuit current and required breaking capacity must be verified. The device does not include integrated residual current protection, so residual protection must be added when required by the installation.