The Schneider Electric Acti9 iC60N A9F75240 miniature circuit breaker is a bipolar automatic circuit breaker rated at 40 A with D curve, designed to protect electrical circuits against overloads and short circuits. It features 2 protected poles, thermal-magnetic tripping technology, and a rated breaking capacity of 6 kA at 400 V AC according to IEC/EN 60898-1. Its D curve is especially suitable for circuits with high inrush currents, such as motors, transformers, and certain inductive loads.
This miniature circuit breaker belongs to the Schneider Electric Acti9 iC60N range and incorporates VisiTrip and VisiSafe technologies, developed to make tripping easier to identify and to increase safety during maintenance operations. Its 2-pole modular format allows DIN rail installation in residential, commercial, and professional electrical panels.
Reference A9F75240 features 2 poles and protection on both poles. Its rated current is 40 A and it uses a D tripping curve with a magnetic threshold of 12 times the rated current, with a tolerance of ±20%.
The D curve is especially suitable for circuits whose loads may generate significant current peaks during startup. This helps reduce nuisance tripping in properly sized applications with motors, transformers, and other equipment with high inrush currents.
The Schneider Electric iC60N combines two tripping mechanisms. Thermal protection responds to sustained overloads that could cause excessive heating in the circuit, while magnetic protection acts quickly when a high short-circuit current occurs.
In this way, the A9F75240 provides comprehensive protection against the main overcurrents that can occur in an electrical circuit.
The miniature circuit breaker has a rated breaking capacity Icn of 6,000 A at 400 V AC in accordance with IEC/EN 60898-1. According to IEC/EN 60947-2, its ultimate breaking capacity Icu depends on the operating voltage.
The main difference between this model and versions with B or C curves is its D tripping curve. Magnetic tripping occurs at higher currents, allowing the inrush current peaks typical of certain loads during startup to be tolerated.
For this reason, it is especially useful in circuits for equipment such as electric motors, transformers, machinery, or inductive loads. The selection of a D curve should be made taking into account the characteristics of the circuit, the impedance of the installation, and the tripping conditions required by the applicable regulations.
The VisiTrip system from Schneider Electric includes a visual trip indication that makes it possible to quickly identify the device that has operated due to an electrical fault.
This function is especially practical in panels with numerous circuits, as it makes diagnosis easier and helps reduce the time needed to locate the tripped protection device.
The VisiSafe technology provides a visual indication that allows the physical opening of the contacts to be checked. The green signal makes downstream maintenance work easier and contributes to a clearer identification of the circuit status.
The A9F75240 is also suitable for isolation in accordance with IEC/EN 60898-1 and IEC/EN 60947-2.
The Acti9 iC60N A9F75240 has a rated insulation voltage Ui of 500 V AC and a rated impulse withstand voltage Uimp of 6 kV. It also features overvoltage category IV and pollution degree 3.
The Acti9 platform allows the miniature circuit breaker to be complemented with electrical auxiliaries, signaling devices, and remote monitoring. It can also be combined with a compatible Vigi residual current block when the installation requires residual current protection.
The residual current block is a separate component and must be selected according to the number of poles, rated current, sensitivity, and the required type of residual current protection.
The Schneider Electric A9F75240 is designed for fixed mounting on a 35 mm DIN rail. It can be connected from the top or bottom and is compatible with comb busbar systems and compatible distribution blocks from the Acti9 range.
Its bipolar format occupies 4 x 9 mm modules, equivalent to a total width of 36 mm or 2 standard 18 mm modules.
The circuit breaker terminals accept rigid and flexible conductors of different cross-sections, making it easy to integrate into properly sized distribution circuits.
The Acti9 iC60N is designed to offer a long service life in electrical panels subject to regular switching operations. Reference A9F75240 achieves a mechanical durability of up to 20,000 cycles and an electrical durability of up to 10,000 cycles.
The power loss indicated for this model is approximately 3.6 W.
The miniature circuit breaker offers an IP20 protection rating as a standalone device and can reach IP40 when installed inside a suitable modular enclosure.
The Schneider Electric Acti9 iC60N A9F75240 2-pole, 40 A, D-curve miniature circuit breaker provides protection against overloads and short circuits in installations with loads that may present high starting currents. Its 6 kA breaking capacity according to IEC/EN 60898-1, 10 kA Icu at 380-415 V according to IEC/EN 60947-2, VisiTrip and VisiSafe technologies, and compatibility with Acti9 auxiliaries make it a robust solution for professional electrical panels.