The Schneider Electric Acti9 iC60N A9F75340 miniature circuit breaker is a 3-pole, 40 A, D-curve automatic circuit breaker designed to protect electrical circuits against overloads and short circuits. Its tripping curve is especially suitable for installations with loads that can generate high inrush currents, such as motors, transformers, and other inductive loads, offering a robust solution for residential, commercial, and industrial electrical panels.
Reference A9F75340 belongs to the Schneider Electric Acti9 iC60N range and features all three poles protected by thermal-magnetic technology. It offers a rated breaking capacity of 6 kA at 400 V AC according to IEC/EN 60898-1 and an ultimate breaking capacity of 10 kA at 380-415 V AC according to IEC/EN 60947-2.
The Schneider Electric A9F75340 has 3 protected poles and a rated current of 40 A. Its D curve features a high magnetic tripping threshold, approximately between 10 and 14 times the rated current according to the characteristics of the iC60 range, making it suitable for circuits where significant current surges occur during startup.
This feature helps reduce nuisance tripping in loads with high starting currents, provided that the selection of the breaker and conductors is made in accordance with the installation’s protection calculations and requirements.
The iC60N combines two protection functions in a single device. The thermal part acts against sustained overloads that could cause excessive heating of the conductors, while the magnetic trip provides rapid operation against high short-circuit currents.
In this way, the A9F75340 protects lines and loads against two of the main overcurrent situations that can occur in an electrical installation.
Schneider Electric specifies for this reference a rated breaking capacity Icn of 6,000 A at 400 V AC in accordance with IEC/EN 60898-1.
According to IEC/EN 60947-2, the ultimate breaking capacity Icu depends on the circuit voltage:
For 6 to 63 A ratings in the iC60N range, the service breaking capacity Ics reaches 75% of Icu under the conditions indicated by IEC/EN 60947-2.
The VisiTrip system makes electrical panel maintenance easier through a visible mechanical indicator on the front of the breaker. When the miniature circuit breaker trips due to an electrical fault, this signal allows the affected device to be identified quickly.
This function is especially useful in panels with numerous circuits, as it helps the installer locate the protection that has operated and reduces the time needed for troubleshooting.
Schneider Electric’s VisiSafe technology provides positive indication of contact opening. The appearance of the green band on the operating handle allows visual verification that the contacts are physically open under the conditions established by the manufacturer.
The A9F75340 is also suitable for industrial isolation according to IEC/EN 60947-2, a particularly relevant feature during interventions and maintenance operations.
The miniature circuit breaker has a rated insulation voltage Ui of 500 V and a rated impulse withstand voltage Uimp of 6 kV.
These characteristics make the device suitable for low-voltage installations that require a high level of insulation and resistance to transient overvoltages.
One of the advantages of the Schneider Electric Acti9 platform is its modular design. The iC60N A9F75340 supports the addition of different electrical auxiliaries for signaling, tripping, and remote monitoring functions.
It can also be combined with compatible Vigi iC60 residual current blocks, allowing residual current protection to be added when required by the installation design.
The Schneider Electric A9F75340 is designed for fixed mounting using a clip on a 35 mm DIN rail. It can be supplied from the top or bottom and is compatible with Acti9 comb busbar systems.
Its double-clip system makes it easy to remove the breaker even when installed alongside a compatible distribution comb, simplifying replacement and maintenance operations inside the panel.
As a three-pole miniature circuit breaker, the device occupies 6 x 9 mm pitches, equivalent to 54 mm or 3 standard 18 mm modules.
The terminals allow conductors to be connected from either the top or the bottom. The A9F75340 accepts suitable cross-sections for properly sized 40 A power circuits.
The Acti9 iC60N is designed to withstand a high number of operations throughout its service life. The device offers mechanical durability of up to 20,000 cycles and electrical durability of up to 10,000 cycles under the conditions specified by Schneider Electric.
The power loss indicated for this reference is approximately 3.6 W.
The miniature circuit breaker has an IP20 protection rating as a standalone device and is designed to operate within a wide ambient temperature range.
The Schneider Electric Acti9 iC60N A9F75340 3-pole, 40 A, D-curve miniature circuit breaker is a particularly suitable solution for protecting three-phase circuits with loads that present high inrush currents. Its 6 kA breaking capacity according to IEC/EN 60898-1 and 10 kA at 380-415 V according to IEC/EN 60947-2, together with VisiTrip and VisiSafe technologies and the possibility of adding auxiliaries and Vigi residual current protection, make it a complete option for professional electrical panels.