The Schneider Electric Acti9 iC60N A9F75410 miniature circuit breaker is a modular device with 4 poles, 10 A rating and D curve, designed to protect electrical circuits against overloads and short circuits. It incorporates thermal-magnetic tripping technology, four protected poles and Acti9 features such as VisiTrip and VisiSafe, making it easier to identify faults and carry out maintenance work in electrical panels.
Reference A9F75410 offers a rated breaking capacity of 6 kA at 400 V AC according to IEC/EN 60898-1 and an ultimate breaking capacity of 10 kA at 380-415 V AC according to IEC/EN 60947-2. Its D curve is especially suitable for circuits with high inrush currents, such as certain motors, transformers, machinery and other inductive loads.
The Schneider Electric A9F75410 features 4 protected poles and a rated current of 10 A. The four poles operate together via a single handle, allowing all conductors associated with the circuit to be disconnected simultaneously.
The D curve has a magnetic tripping threshold higher than B and C curves, allowing it to withstand high transient currents during the start-up of certain loads without nuisance tripping.
Schneider Electric specifies for the A9F75410 a magnetic tripping threshold of 12 times the rated current, with a tolerance of ±20 %.
This makes it especially suitable for circuits supplying:
The selection of a D curve should be made by checking that the available short-circuit current in the installation allows disconnection within the required times.
The Acti9 iC60N combines two protection mechanisms in a single device:
This combination helps protect downstream circuits against the main overcurrent situations.
In installations evaluated according to IEC/EN 60898-1, the Schneider Electric A9F75410 has a rated breaking capacity Icn of 6,000 A at 400 V AC and 50/60 Hz.
This value corresponds to the breaking capacity commonly used for circuit breakers intended for domestic and similar installations.
According to IEC/EN 60947-2, the ultimate breaking capacity Icu varies depending on the operating voltage:
For this reason, the commercial values of 6 kA and 10 kA correspond to different standards and test conditions and must be interpreted together with the operating voltage.
The iC60N A9F75410 is suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2. This feature allows it to be used as a circuit isolation device within the conditions established by the manufacturer.
The VisiTrip system provides a front indication when the circuit breaker has tripped due to a fault. This makes it possible to quickly identify the affected circuit in panels with numerous devices and speeds up diagnostic tasks.
VisiSafe technology provides a visual indication of safe contact opening. The green band visible when the device is open helps confirm circuit isolation before certain maintenance operations.
The Schneider Electric A9F75410 has an energy limiting class 3 according to IEC/EN 60898-1. This capability helps limit the energy flowing through the circuit during a short circuit, reducing the thermal and electrodynamic stresses transmitted to downstream conductors and equipment.
The circuit breaker is designed for fixed installation using a clip-on DIN rail mount, making it easy to integrate into distribution boards together with RCDs, contactors and other Acti9 devices.
The Acti9 iC60 range allows power supply from the top or bottom, offering greater flexibility when arranging panel wiring. It is also compatible with suitable Acti9 comb busbar distribution systems.
The A9F75410 includes screw terminals for rigid and flexible conductors:
The modular architecture of the Acti9 range makes it possible to complement the circuit breaker with different compatible accessories. Depending on the panel requirements, signalling auxiliaries, remote tripping, monitoring and Vigi residual current blocks can be added.
Exact compatibility must be checked for each accessory and specific configuration.
The Schneider Electric A9F75410 is designed to provide a long service life in electrical distribution installations.
The device has an IP20 protection rating according to IEC 60529. When correctly installed inside a suitable enclosure, it can achieve a protection rating of up to IP40.
This wide thermal range allows the iC60N to be used in many professional installation environments, always within the mounting and derating conditions indicated by Schneider Electric.
The declared power loss for this reference is approximately 2.3 W. This data can be used to calculate the total thermal dissipation of panels incorporating numerous modular devices.
The Schneider Electric Acti9 iC60N A9F75410 combines four protected poles, a 10 A rating and D curve in a device especially suitable for circuits with high transient currents. Its thermal and magnetic protection allows it to act both against prolonged overloads and short circuits.
The 6 kA breaking capacity according to IEC 60898-1 and 10 kA at 380-415 V according to IEC 60947-2, together with VisiTrip and VisiSafe technologies, energy limiting class 3 and the possibility of adding auxiliaries and Vigi blocks, make this reference a versatile solution for professional electrical panels and distribution applications.