The Schneider Electric Acti9 iC60N A9F75463 miniature circuit breaker is a modular device with 4 poles, 63 A and D tripping curve, designed to protect electrical circuits against overloads and short circuits. It offers a breaking capacity of 6 kA according to IEC/EN 60898-1 at 400 V AC and 10 kA Icu according to IEC/EN 60947-2 at 380-415 V AC, making it suitable for electrical distribution boards in residential, commercial and industrial applications.
The A9F75463 reference belongs to Schneider Electric's Acti9 iC60 range and incorporates technologies such as VisiTrip, to make it easier to identify tripped circuits, and VisiSafe, which provides a safe indication of the physical opening of the contacts. Its D curve is especially suitable for circuits with high inrush currents, such as certain motors, transformers and other loads with strong connection surges.
The Acti9 iC60N A9F75463 has 4 protected poles and a rated current of 63 A. All poles are disconnected by the same operating mechanism, allowing the circuit conductors to be protected and isolated simultaneously.
The D curve has a higher magnetic threshold than B and C curves, reducing the risk of nuisance tripping when switching on loads that generate significant current peaks during start-up.
Schneider Electric specifies for this reference a magnetic tripping threshold of approximately 12 times the rated current, with a tolerance of ±20%.
This makes it especially suitable for applications such as:
The choice of a D curve should be made after checking the load characteristics, the available short-circuit current and the disconnection conditions required by the installation.
The A9F75463 uses a thermal-magnetic trip unit that combines two protection functions:
This combination helps protect downstream conductors and circuits against the main overcurrent situations.
For applications compliant with IEC/EN 60898-1, Schneider Electric declares a rated breaking capacity Icn of 6,000 A at 400 V AC and 50/60 Hz.
This standard is commonly applied to circuit breakers intended for domestic and similar electrical installations.
When considering the industrial standard IEC/EN 60947-2, the ultimate breaking capacity Icu varies depending on the circuit voltage:
For this reason, the usual commercial designation 6 kA / 10 kA refers to different standards and test conditions and does not represent two directly interchangeable values.
The Schneider Electric iC60N A9F75463 is suitable for isolation in accordance with IEC/EN 60898-1 and IEC/EN 60947-2. This feature allows it to be used to electrically isolate the circuit within the conditions defined by the standards and the manufacturer.
The VisiTrip system makes it easy to identify the breaker that has tripped due to an electrical fault. The front indicator allows the affected circuit to be quickly located within a panel with numerous devices.
This function can reduce the time needed to locate faults and speed up maintenance and service restoration tasks.
Schneider Electric's VisiSafe system provides a visual indication confirming the effective opening of the contacts when the breaker is in the open position.
This feature provides greater safety during maintenance operations on circuits downstream of the miniature circuit breaker.
The breaker is designed for integration into low-voltage distribution boards and has insulation characteristics suitable for professional applications.
The Acti9 iC60N has an energy limiting class 3 according to IEC/EN 60898-1. A high limiting capacity helps reduce the energy passing through the circuit during a short circuit before the device completes disconnection.
This feature helps reduce the thermal and electrodynamic stresses suffered by downstream conductors and equipment.
The Schneider Electric A9F75463 is designed for fixed DIN rail mounting, making it easy to integrate alongside other modular devices in the Acti9 family.
The miniature circuit breaker has terminals prepared for connection of rigid or flexible conductors, facilitating installation in power electrical panels.
The declared power loss for the A9F75463 is approximately 5.6 W under nominal conditions, a relevant figure when calculating total heat dissipation inside electrical panels with multiple devices.
The Acti9 iC60N is designed to operate in demanding conditions and supports a wide ambient temperature range.
The Acti9 platform allows the iC60N to be complemented with various accessories and auxiliary devices to expand its functions. Depending on the project, signalling elements, remote tripping, monitoring or residual current protection via compatible Vigi blocks can be added.
The exact compatibility of each accessory should be checked against the specific breaker configuration and Schneider Electric's current documentation.
The Schneider Electric A9F75463 complies with the main international standards applicable to low-voltage thermal-magnetic circuit breakers:
The Schneider Electric Acti9 iC60N A9F75463 combines a rated current of 63 A, four protected poles and a D curve in a miniature circuit breaker especially suitable for circuits where high currents may occur when loads are switched on.
Its breaking capacity of 6 kA according to IEC 60898-1 and 10 kA at 400 V according to IEC 60947-2, together with VisiTrip and VisiSafe technologies, energy limiting class 3 and the possibility of incorporating Acti9 auxiliaries, make it a versatile solution for distribution boards and professional applications.