The Schneider Electric Acti9 iC60N A9F78210 thermal-magnetic circuit breaker is a bipolar automatic switch rated at 10 A with B curve, designed to protect electrical circuits against overloads and short circuits. It features 2 poles with both poles protected, thermal-magnetic tripping technology, and a rated breaking capacity of 6 kA at 400 V AC according to IEC/EN 60898-1.
Reference A9F78210 belongs to Schneider Electric’s professional Acti9 iC60N range and incorporates VisiTrip and VisiSafe technologies, making it easier to identify trips and check contact status. It can operate on AC and DC networks and supports the addition of compatible auxiliaries and Vigi residual current blocks.
The Schneider Electric A9F78210 has a configuration of 2 poles with 2 protected poles and a rated current of 10 A. Its B tripping curve provides a magnetic threshold of 4 times the rated current with a ±20% tolerance according to IEC/EN 60947-2.
This curve trips magnetically at lower currents than C or D curves, making it suitable for properly sized circuits whose loads do not generate high inrush currents.
The Acti9 iC60N combines two protection mechanisms. The thermal trip acts against sustained overloads that can cause excessive heating of the conductors, while the magnetic trip provides rapid disconnection in the event of high short-circuit currents.
This combination makes it possible to protect electrical distribution lines and circuits with a single modular device.
Schneider Electric declares for the A9F78210 a rated breaking capacity Icn of 6,000 A at 400 V AC in accordance with IEC/EN 60898-1.
According to IEC/EN 60947-2, the ultimate breaking capacity Icu depends on the operating voltage:
Therefore, at 400 V AC the device offers 6 kA according to IEC/EN 60898-1 and 10 kA according to IEC/EN 60947-2, so it is important to always specify the reference standard when comparing breaking capacities.
The service breaking capacity Ics specified according to IEC/EN 60947-2 reaches:
According to IEC/EN 60898-1, the service breaking capacity reaches 6 kA at 400 V AC.
The VisiTrip system provides a front indicator that makes it easy to locate the circuit breaker that has tripped due to an electrical fault. This feature is especially useful in panels with multiple circuits and helps speed up diagnosis and maintenance tasks.
VisiSafe technology allows the open contact status to be visually checked. The device is also suitable for isolation in accordance with IEC/EN 60898-1 and IEC/EN 60947-2.
The circuit breaker has a rated insulation voltage Ui of 500 V AC and a rated impulse withstand voltage Uimp of 6 kV, providing suitable insulation performance for low-voltage distribution installations.
The Acti9 iC60N A9F78210 can be complemented with electrical auxiliaries, remote monitoring devices, and compatible Vigi residual current blocks, allowing the control, signaling, and protection functions of the panel to be expanded.
Residual current protection is not integrated in this circuit breaker and must be added with a compatible device when required.
The A9F78210 is designed for fixed mounting on a DIN rail. Its bipolar format occupies 4 x 9 mm modules, equivalent to 36 mm in width or 2 standard 18 mm modules.
The circuit breaker supports connection from either the top or the bottom and is compatible with comb busbars and suitable distribution blocks from the Acti9 range.
The Schneider Electric Acti9 iC60N is designed to withstand a high number of operations throughout its service life:
The A9F78210 offers an IP20 protection rating and is designed to be installed inside a suitable electrical panel or enclosure.
The Schneider Electric Acti9 iC60N A9F78210 2-pole, 10 A, B-curve thermal-magnetic circuit breaker provides protection against overloads and short circuits in low-voltage distribution circuits. Its 6 kA breaking capacity according to IEC/EN 60898-1, 10 kA capacity at 380-415 V according to IEC/EN 60947-2, VisiTrip and VisiSafe technologies, and compatibility with Acti9 auxiliaries make it suitable for integration into residential, commercial, and professional electrical panels.