The Schneider Electric Acti9 iC60N A9F75216 miniature circuit breaker is a bipolar automatic circuit breaker rated at 16 A with D curve, designed to protect electrical circuits against overloads and short circuits. It features 2 protected poles, thermal-magnetic tripping, and a breaking capacity of 6 kA at 400 V AC according to IEC/EN 60898-1, making it especially suitable for circuits with loads that have high inrush currents.
The A9F75216 reference belongs to Schneider Electric's professional Acti9 iC60N range and incorporates VisiTrip and VisiSafe technologies, which make it easy to identify tripping events and verify contact status. It can be used in AC and DC networks and supports the addition of compatible auxiliaries and Vigi residual current blocks.
The Schneider Electric A9F75216 has 2 poles with both poles protected and a rated current of 16 A. Its D curve provides a magnetic threshold of 12 times the rated current, with a tolerance of ±20%.
This feature allows it to withstand high current peaks during the start-up of certain loads, making the D curve suitable for properly sized applications with motors, transformers, and other loads with strong starting currents.
The Acti9 iC60N combines thermal and magnetic protection in a single device. The thermal element acts against sustained overloads that could cause excessive heating of the conductors, while the magnetic trip enables rapid disconnection when a high short-circuit current occurs.
This combination provides protection for lines and distribution circuits within low-voltage electrical panels.
The A9F75216 offers a rated breaking capacity Icn of 6,000 A at 400 V AC in accordance with IEC/EN 60898-1. According to IEC/EN 60947-2, its breaking capacity varies depending on the operating voltage:
At 380-415 V AC, the service breaking capacity Ics reaches 7.5 kA, equivalent to 75% of Icu according to IEC/EN 60947-2. According to IEC/EN 60898-1, Ics reaches 6 kA at 400 V AC.
The D curve sets this model apart from B or C curve versions. Its higher magnetic threshold allows it to tolerate short-duration current surges generated during the start-up of certain loads without causing nuisance tripping.
When selecting a D curve miniature circuit breaker, the available short-circuit current, line impedance, conductor cross-section, and the characteristics of the protected load must be taken into account.
The VisiTrip technology includes a front indicator that makes it easy to quickly identify that the circuit breaker has operated due to an electrical fault. This signaling is especially useful in panels with numerous circuits, simplifying diagnosis and maintenance tasks.
The VisiSafe system allows visual verification of the physical opening of the contacts, helping maintenance operations with a clear identification of the switch status.
The A9F75216 is also suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2.
The miniature circuit breaker offers a rated insulation voltage Ui of 500 V AC and a rated impulse withstand voltage Uimp of 6 kV, as well as overvoltage category IV.
The Schneider Electric Acti9 iC60N can be complemented with electrical auxiliaries, remote monitoring devices, and compatible Vigi residual current blocks. This modularity makes it possible to expand signaling, tripping, control, or residual current protection functions according to the needs of the panel.
Residual current protection is not integrated in the A9F75216 reference and must be added with a compatible device when required.
The miniature circuit breaker is designed for fixed mounting on a DIN rail and supports connection via compatible comb busbar from both the top and bottom.
Its bipolar format occupies 4 modules of 9 mm, equivalent to 36 mm in width.
The terminals accept wiring from the top or bottom and are prepared for the following cross-sections:
The Acti9 iC60N A9F75216 is designed to withstand a high number of operations throughout its service life.
The device offers an IP20 protection rating according to IEC/EN 60529 and is designed to be installed inside a suitable electrical enclosure or panel.
The Schneider Electric Acti9 iC60N A9F75216 2-pole, 16 A, D curve provides complete protection against overloads and short circuits in circuits with high inrush currents. Its 6 kA breaking capacity according to IEC/EN 60898-1, 10 kA capacity at 380-415 V according to IEC/EN 60947-2, VisiTrip and VisiSafe systems, and compatibility with Acti9 auxiliaries make it suitable for integration into professional electrical panels with demanding protection requirements.