IC60N Circuit Breaker 2P 25A Curve D with reference A9F75225 from the brand SCHNEIDER ELECTRIC
IC60N Circuit Breaker 2P 25A Curve D with reference A9F75225 from the brand SCHNEIDER ELECTRIC
SCHNEIDER ELECTRIC

IC60N Circuit Breaker 2P 25A Curve D

REF
A9F75225
(0)
81.10 €
€81.10
€365.46
Up to -6% for professionals. Discover it.
Schneider Electric Acti9 iC60N 2P 25 A circuit breaker, D curve and 6 kA breaking capacity. Protects circuits with high inrush currents against overloads and short circuits.
Buy now and receive it between 20 and November 23
Express delivery
Get +82 +163 Sumis for the purchase
Receive 2x Sumis for a limited time
More about the product

Information about IC60N Circuit Breaker 2P 25A Curve D

The Schneider Electric Acti9 iC60N A9F75225 miniature circuit breaker is a low-voltage modular circuit breaker designed to protect electrical circuits against overloads and short circuits. It features 2 protected poles, a rated current of 25 A, and D tripping curve, making it especially suitable for circuits that may present high inrush currents.

Its thermal-magnetic trip unit combines thermal protection against prolonged overloads and fast magnetic tripping in the event of short circuits. It offers a breaking capacity of 6000 A at 400 V AC according to IEC/EN 60898-1 and 10 kA at 380-415 V AC according to IEC/EN 60947-2. It also incorporates Schneider Electric’s VisiTrip and VisiSafe technologies to make fault identification easier and improve safety during maintenance operations.

25 A two-pole miniature circuit breaker with D curve

Reference A9F75225 has a 2P configuration, with protection on both poles, and a rated current of 25 A. The D curve has a higher magnetic threshold, allowing it to withstand higher-than-normal inrush currents for a short period before instantaneous tripping occurs.

Schneider Electric specifies a magnetic tripping threshold of 12 times the rated current ±20 %. This makes the D curve especially suitable for certain motors, transformers, inductive loads, and other receivers that can generate strong current surges during connection.

Thermal and magnetic protection

The Acti9 iC60N uses thermal-magnetic tripping technology to provide two complementary protection functions:

  • Thermal protection: operates when an overload causes a current above the rated value for a certain period of time.
  • Magnetic protection: acts quickly against very high currents caused by a short circuit.

This combination protects both the conductors and the downstream connected equipment against the main overcurrents that can occur in an electrical circuit.

Breaking capacity according to installation voltage

The interrupting capacity of the A9F75225 varies depending on the voltage and the reference standard. Schneider Electric specifies:

  • 6000 A Icn at 400 V AC according to IEC/EN 60898-1.
  • 36 kA Icu between 12 and 133 V AC according to IEC/EN 60947-2.
  • 20 kA Icu between 220 and 240 V AC according to IEC/EN 60947-2.
  • 10 kA Icu between 380 and 415 V AC according to IEC/EN 60947-2.
  • 6 kA Icu at 440 V AC according to IEC/EN 60947-2.
  • 10 kA Icu up to 125 V DC according to IEC/EN 60947-2.

The service breaking capacity Ics reaches 75% of the Icu in the main AC configurations indicated by the manufacturer.

VisiTrip technology for fault location

The miniature circuit breaker incorporates Schneider Electric’s VisiTrip system. This visual indicator makes it easy to quickly identify that the breaker has tripped due to an electrical fault.

In panels with many circuits, this signaling helps locate the device that has operated more quickly, reducing the time needed for diagnostics and maintenance tasks.

VisiSafe for checking contact opening

The VisiSafe technology provides a visible indication of the open contact state. The green front band allows you to verify that the circuit is physically open, providing an additional safety reference before carrying out downstream interventions.

The A9F75225 is also suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2.

Class 3 current limiting

The Acti9 iC60N has a current limiting class 3 according to IEC/EN 60898-1. This feature helps limit the energy flowing through the circuit during certain short circuits, helping reduce the thermal and electrodynamic stresses on conductors and equipment downstream.

Compatible with AC and DC current

The Schneider Electric A9F75225 can be used in AC networks as well as in certain DC applications, always within the electrical limits specified by the manufacturer.

In AC, it operates at a frequency of 50/60 Hz. For DC, Schneider Electric specifies a breaking capacity of up to 10 kA at voltages up to 125 V DC.

Modular DIN rail mounting

The miniature circuit breaker is designed for fixed installation on a DIN rail. It occupies two standard modules, with a total width of 36 mm, making it easy to integrate alongside other Acti9 devices inside modular electrical panels.

  • Height: 85 mm.
  • Width: 36 mm.
  • Depth: 78.5 mm.
  • Installation depth: approximately 44.5 mm.
  • Approximate weight: 0.25 kg.

Electrical connections

The A9F75225 accepts conductor connections via screw terminals, with different cross-sections depending on the type of cable used:

  • Rigid conductor: 1 to 25 mm².
  • Flexible conductor: 1 to 16 mm².

Its modular design also allows the use of compatible distribution systems and accessories from the Acti9 family to simplify the supply of multiple devices within the panel.

Compatible with auxiliaries and Vigi residual current blocks

The Acti9 iC60N supports the addition of electrical auxiliaries, signaling devices, remote monitoring systems, and compatible Vigi residual current blocks.

This modularity makes it possible to expand the functions of the miniature circuit breaker when the installation requires remote tripping, status signaling, or additional residual current protection.

IP20 protection

The breaker has an IP20 protection rating at its terminals according to IEC/EN 60529. When correctly installed in a class II insulated modular enclosure, the assembly can achieve IP40 protection under the conditions specified by Schneider Electric.

Durability for professional installations

The fast-closing mechanism of the iC60 range helps reduce contact wear and extend the service life of the device. Schneider Electric specifies:

  • Mechanical durability: up to 20,000 cycles.
  • Electrical durability: up to 10,000 cycles.

The device is designed to operate at ambient temperatures between -35 and 70 °C, allowing use in a wide range of installation conditions.

Technical characteristics of the Schneider Electric A9F75225

  • Brand: Schneider Electric.
  • Reference: A9F75225.
  • Range: Acti9.
  • Product: Acti9 iC60N.
  • Type: modular thermal-magnetic circuit breaker.
  • Application: electrical distribution.
  • Number of poles: 2P.
  • Protected poles: 2.
  • Rated current: 25 A.
  • Tripping curve: D.
  • Tripping technology: thermal-magnetic.
  • Magnetic threshold: 12 x In ±20 %.
  • Network type: AC and DC.
  • Frequency: 50/60 Hz.
  • Breaking capacity Icn: 6 kA at 400 V AC according to IEC/EN 60898-1.
  • Breaking capacity Icu: 20 kA at 220-240 V AC according to IEC/EN 60947-2.
  • Breaking capacity Icu: 10 kA at 380-415 V AC according to IEC/EN 60947-2.
  • Breaking capacity Icu: 6 kA at 440 V AC according to IEC/EN 60947-2.
  • Breaking capacity Icu: 10 kA up to 125 V DC according to IEC/EN 60947-2.
  • Utilization category: A.
  • Limiting class: 3.
  • Rated insulation voltage Ui: 500 V AC.
  • Impulse withstand voltage Uimp: 6 kV.
  • Suitable for isolation: yes.
  • Trip indicator: VisiTrip.
  • Safe opening indicator: VisiSafe.
  • Mounting: fixed on DIN rail.
  • Width: 36 mm.
  • Height: 85 mm.
  • Depth: 78.5 mm.
  • Protection rating: IP20.
  • Rigid conductor: 1-25 mm².
  • Flexible conductor: 1-16 mm².
  • Mechanical durability: 20,000 cycles.
  • Electrical durability: 10,000 cycles.
  • Operating temperature: -35 to 70 °C.
  • Pollution degree: 3.
  • Overvoltage category: IV.
  • Power loss: approximately 3 W.
  • Standards: IEC/EN 60898-1 and IEC/EN 60947-2.
  • EAN: 3606480080982.

D-curve miniature circuit breaker for loads with high inrush currents

The Schneider Electric A9F75225 is especially suitable for circuits where loads can generate high current peaks at startup. Its D curve allows these transient currents to be tolerated within its tripping limits, reducing the risk of nuisance tripping in properly sized applications.

The combination of 2 poles, 25 A, D curve, 6 kA breaking capacity, VisiTrip and VisiSafe technologies, and compatibility with Acti9 auxiliaries provides a robust and flexible solution for circuit protection in residential, commercial, and industrial electrical panels.

Specifications
Manufacturer
SCHNEIDER ELECTRIC
Reference
A9F75225
SKU
SCH37265FFE
Object
Magnetic circuit breaker
Number of poles
Assembly
Fixed
Nominal current
25 A
Network type
CA, CC
Protection rating
IP20
Frequency
50.00 - 60.00 Hz
Datasheets
Reviews
Returns within 30 days
Shop with peace of mind. If something goes wrong, we'll take care of it.
After-sales service
Any questions? Our support team will be happy to help you.
Pay how and when you want
Card, bank transfer, PayPal... Installment? We have them all.
GroupSumi is your online distributor for construction, electrical material and climate control.
All rights reserved © 2026 GroupSumi