The Schneider Electric Acti9 iC60N A9F75225 miniature circuit breaker is a low-voltage modular circuit breaker designed to protect electrical circuits against overloads and short circuits. It features 2 protected poles, a rated current of 25 A, and D tripping curve, making it especially suitable for circuits that may present high inrush currents.
Its thermal-magnetic trip unit combines thermal protection against prolonged overloads and fast magnetic tripping in the event of short circuits. It offers a breaking capacity of 6000 A at 400 V AC according to IEC/EN 60898-1 and 10 kA at 380-415 V AC according to IEC/EN 60947-2. It also incorporates Schneider Electric’s VisiTrip and VisiSafe technologies to make fault identification easier and improve safety during maintenance operations.
Reference A9F75225 has a 2P configuration, with protection on both poles, and a rated current of 25 A. The D curve has a higher magnetic threshold, allowing it to withstand higher-than-normal inrush currents for a short period before instantaneous tripping occurs.
Schneider Electric specifies a magnetic tripping threshold of 12 times the rated current ±20 %. This makes the D curve especially suitable for certain motors, transformers, inductive loads, and other receivers that can generate strong current surges during connection.
The Acti9 iC60N uses thermal-magnetic tripping technology to provide two complementary protection functions:
This combination protects both the conductors and the downstream connected equipment against the main overcurrents that can occur in an electrical circuit.
The interrupting capacity of the A9F75225 varies depending on the voltage and the reference standard. Schneider Electric specifies:
The service breaking capacity Ics reaches 75% of the Icu in the main AC configurations indicated by the manufacturer.
The miniature circuit breaker incorporates Schneider Electric’s VisiTrip system. This visual indicator makes it easy to quickly identify that the breaker has tripped due to an electrical fault.
In panels with many circuits, this signaling helps locate the device that has operated more quickly, reducing the time needed for diagnostics and maintenance tasks.
The VisiSafe technology provides a visible indication of the open contact state. The green front band allows you to verify that the circuit is physically open, providing an additional safety reference before carrying out downstream interventions.
The A9F75225 is also suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2.
The Acti9 iC60N has a current limiting class 3 according to IEC/EN 60898-1. This feature helps limit the energy flowing through the circuit during certain short circuits, helping reduce the thermal and electrodynamic stresses on conductors and equipment downstream.
The Schneider Electric A9F75225 can be used in AC networks as well as in certain DC applications, always within the electrical limits specified by the manufacturer.
In AC, it operates at a frequency of 50/60 Hz. For DC, Schneider Electric specifies a breaking capacity of up to 10 kA at voltages up to 125 V DC.
The miniature circuit breaker is designed for fixed installation on a DIN rail. It occupies two standard modules, with a total width of 36 mm, making it easy to integrate alongside other Acti9 devices inside modular electrical panels.
The A9F75225 accepts conductor connections via screw terminals, with different cross-sections depending on the type of cable used:
Its modular design also allows the use of compatible distribution systems and accessories from the Acti9 family to simplify the supply of multiple devices within the panel.
The Acti9 iC60N supports the addition of electrical auxiliaries, signaling devices, remote monitoring systems, and compatible Vigi residual current blocks.
This modularity makes it possible to expand the functions of the miniature circuit breaker when the installation requires remote tripping, status signaling, or additional residual current protection.
The breaker has an IP20 protection rating at its terminals according to IEC/EN 60529. When correctly installed in a class II insulated modular enclosure, the assembly can achieve IP40 protection under the conditions specified by Schneider Electric.
The fast-closing mechanism of the iC60 range helps reduce contact wear and extend the service life of the device. Schneider Electric specifies:
The device is designed to operate at ambient temperatures between -35 and 70 °C, allowing use in a wide range of installation conditions.
The Schneider Electric A9F75225 is especially suitable for circuits where loads can generate high current peaks at startup. Its D curve allows these transient currents to be tolerated within its tripping limits, reducing the risk of nuisance tripping in properly sized applications.
The combination of 2 poles, 25 A, D curve, 6 kA breaking capacity, VisiTrip and VisiSafe technologies, and compatibility with Acti9 auxiliaries provides a robust and flexible solution for circuit protection in residential, commercial, and industrial electrical panels.