The Schneider Electric Acti9 iC60N A9F79240 miniature circuit breaker is a modular device with 2 protected poles, 40 A and C curve, designed to protect electrical circuits against overloads and short circuits. It incorporates thermal-magnetic tripping technology, VisiTrip and VisiSafe signaling systems and DIN rail mounting, offering a reliable solution for residential, commercial and professional electrical panels.
Reference A9F79240 belongs to Schneider Electric's Acti9 iC60N range and provides a rated breaking capacity Icn of 6 kA at 400 V AC according to IEC/EN 60898-1. For applications evaluated according to IEC/EN 60947-2, it reaches an ultimate breaking capacity Icu of 10 kA at 380-415 V AC and up to 20 kA at 220-240 V AC.
The Schneider Electric A9F79240 has 2 protected poles and a rated current of 40 A. Both poles incorporate overcurrent protection and are operated simultaneously by a single front lever.
The iC60N combines two complementary protection mechanisms in a single device:
This combination makes it possible to effectively protect downstream conductors and loads against the main overcurrent situations.
The C curve is especially suitable for circuits that may present moderate transient currents during startup, and is one of the most widely used curves in general electrical distribution.
Schneider Electric specifies for this family a magnetic threshold of 8 times the rated current with a tolerance of ±20%. In the A9F79240, this behavior allows it to withstand certain inrush peaks without losing the ability to act quickly in the event of a short circuit.
The C curve is commonly used in applications such as:
The final selection of the rating and curve must take into account conductor cross-section, load characteristics, available short-circuit current and installation disconnection requirements.
According to IEC/EN 60898-1, Schneider Electric specifies for this reference a rated breaking capacity Icn of 6,000 A at 400 V AC and 50/60 Hz.
This value corresponds to the short-circuit breaking capacity established for circuit breakers intended for domestic and similar installations.
When the circuit breaker is evaluated in accordance with IEC/EN 60947-2, the ultimate breaking capacity Icu depends on the operating voltage.
For this reason, the commercial designation 6 kA / 10 kA refers to values obtained under different standards and test conditions.
Schneider Electric also specifies the following service breaking capacity values according to IEC/EN 60947-2:
These values are equivalent to 75% of the ultimate breaking capacity Icu at the indicated voltages.
The Schneider Electric Acti9 iC60N A9F79240 is suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2. This feature allows it to be used to electrically isolate the circuit within the conditions specified by the manufacturer.
The VisiSafe technology provides a visual indication designed to reliably confirm that the contacts are physically open when the circuit breaker is in the OFF position.
This feature facilitates maintenance tasks and increases safety during interventions on the downstream circuit.
The VisiTrip system provides a specific front indication when the miniature circuit breaker has tripped due to an electrical fault.
In panels with numerous circuits, this indication makes it possible to quickly locate the device that has operated, reducing the time needed to identify the affected circuit and carry out diagnostic tasks.
The Acti9 iC60N offers an energy limiting class 3 according to IEC/EN 60898-1. The ability to limit current and energy during a short circuit helps reduce the thermal and electrodynamic stresses received by downstream conductors and devices.
The A9F79240 has insulation characteristics suitable for use in low-voltage electrical panels:
The Schneider Electric A9F79240 can be used in certain AC and DC networks, always respecting the voltages and breaking capacities specifically indicated by the manufacturer.
In DC, Schneider Electric specifies a breaking capacity of 10 kA Icu up to 125 V DC for this configuration.
The miniature circuit breaker is designed for modular installation by means of a clip-on 35 mm DIN rail. Its compact format makes it easy to integrate alongside residual current devices, contactors, surge protection devices and other Acti9 components.
The Acti9 iC60N design allows power supply connection from either the top or bottom, offering flexibility when organizing the wiring and distribution systems in the panel.
It can also be integrated with comb busbars and compatible accessories from the Acti9 range.
Reference A9F79240 has screw terminals prepared for rigid and flexible conductors:
These connection capacities are suitable for the 40 A rating and facilitate professional panel wiring.
The Schneider Electric iC60N can be complemented with different Acti9 electrical auxiliaries and accessories to expand its monitoring and control functions.
Depending on the configuration, the following can be added:
Exact compatibility must be checked according to the chosen accessory and panel configuration.
The A9F79240 can be combined with compatible iC60 Vigi residual current blocks, allowing residual current protection to be added to the miniature circuit breaker assembly.
This makes it easier to create modular systems that combine protection against overloads, short circuits and earth leakage using coordinated Acti9 components.
The Acti9 iC60N is designed for a long service life in electrical panels:
This resistance makes it suitable for installations where periodic opening and closing operations are required throughout the service life of the panel.
The device has an IP20 protection rating according to IEC 60529. When correctly installed inside a suitable modular enclosure, it can achieve a protection rating of up to IP40.
The Schneider Electric A9F79240 is designed to operate in demanding environmental conditions:
The A9F79240 complies with the main standards applicable to low-voltage miniature circuit breakers:
The Schneider Electric Acti9 iC60N A9F79240 combines 2 protected poles, 40 A and C curve in a compact miniature circuit breaker designed to protect circuits against overloads and short circuits. Its tripping curve is especially suitable for numerous distribution circuits with moderate starting loads.
The 6 kA breaking capacity according to IEC 60898-1 and 10 kA at 380-415 V according to IEC 60947-2, together with VisiTrip, VisiSafe, limiting class 3 and the possibility of adding Vigi blocks and Acti9 auxiliaries, make the A9F79240 a versatile solution for residential, commercial and professional electrical panels.