The Schneider Electric Acti9 iC60N A9F75204 miniature circuit breaker is a modular 2-pole, 4 A, D-curve circuit breaker designed to protect electrical circuits against overloads and short circuits. It features 2 protected poles and offers a breaking capacity of 6 kA at 400 V AC according to IEC/EN 60898-1, reaching up to 50 kA according to IEC/EN 60947-2 within the voltage ranges specified by Schneider Electric.
Its D-curve tripping characteristic makes it especially suitable for circuits with high inrush current, provided the protection is correctly sized. It is part of the modular Acti9 iC60N range and incorporates VisiTrip and VisiSafe technologies to make tripping easier to identify and to visually check the safe state of the circuit.
The Acti9 iC60N combines two protection systems. The thermal trip acts when a sustained overload occurs, while the magnetic trip responds quickly to high currents caused by a short circuit.
This combination helps protect conductors and equipment against two of the main electrical faults that can occur in a low-voltage installation.
The A9F75204 reference uses a D tripping curve. Schneider Electric specifies a magnetic threshold for this version of approximately 12 times the rated current, with a tolerance of ±20%.
The D curve allows it to withstand higher transient inrush currents than those typically permitted by a B or C curve before the instantaneous magnetic trip operates. For this reason, it is often used in properly designed circuits supplying loads with significant starting peaks.
The choice of a D curve should be made by checking the circuit impedance, the available short-circuit current and the automatic disconnection requirements established for the installation.
The A9F75204 is a 2P bipolar miniature circuit breaker with thermomagnetic protection on both poles. The two connected conductors are disconnected simultaneously when a manual operation or an automatic trip occurs.
This configuration distinguishes it from 1P+N devices, where only the phase pole normally includes overcurrent protection.
Schneider Electric declares a rated breaking capacity Icn of 6,000 A at 400 V AC and 50/60 Hz in accordance with IEC/EN 60898-1.
The breaking capacity determines the short-circuit current that the circuit breaker can safely interrupt under the conditions specified by the standard. Before installing the device, it should be verified that this value is suitable for the prospective short-circuit current at the installation point.
When evaluated according to IEC/EN 60947-2, the iC60N offers an Icu breaking capacity of up to 50 kA across different AC voltage ranges.
These values make the iC60N suitable for distribution boards where a high interrupting capacity is required, always within the operating conditions defined by Schneider Electric.
The A9F75204 has limiting class 3 according to IEC/EN 60898-1. This limiting capability helps reduce the energy passing through the circuit during a short circuit, helping to reduce thermal and electrodynamic stress on downstream conductors and equipment.
The VisiTrip system provides a visual indication that makes it easy to quickly identify that the circuit breaker has tripped due to an electrical fault.
In panels with many circuits, this indication helps locate the affected device and can reduce the time needed to diagnose an incident.
The VisiSafe function uses a green indication to visually confirm the physical opening of the contacts. This feature is intended to provide a clear reference of the circuit isolation state before downstream work is carried out.
The device is also specified as suitable for isolation in accordance with the applicable standards indicated by Schneider Electric.
The Acti9 iC60 range incorporates a fast-closing mechanism independent of the speed at which the user operates the handle. This system helps ensure consistent contact behavior during each closing operation and contributes to improved device durability.
Schneider Electric declares a high service life for the iC60N:
These figures correspond to the test conditions established by the manufacturer and make the miniature circuit breaker suitable for installations where reliability is required over a large number of operations.
The A9F75204 is designed for fixed mounting on a DIN rail inside modular electrical panels. It occupies four 9 mm pitches, equivalent to 2 modules of 18 mm.
The Acti9 system allows the miniature circuit breaker to be integrated with other protection, control and signaling devices and supports connection via compatible comb busbars at the top or bottom.
Its standardized dimensions make it easy to integrate into modular panels alongside the rest of the Acti9 protection devices.
The miniature circuit breaker has upper and lower connection terminals for copper conductors. For this rating, the permitted cross-sections include:
The actual conductor cross-section should be selected according to the design current, installation method, voltage drop, temperature and applicable electrical regulations.
The Schneider Electric A9F75204 has a rated insulation voltage Ui of 500 V and an impulse withstand voltage Uimp of 6 kV. It is also classified under overvoltage category IV and pollution degree 3.
The device has a degree of protection IP20 according to IEC 60529. Once installed inside a suitable enclosure, the assembly can achieve higher protection levels depending on the characteristics of the panel used.
The iC60N is designed to operate in demanding environmental conditions:
The modular architecture of the range allows the A9F75204 to be combined with compatible Acti9 electrical auxiliaries and accessories. This makes it possible to add signaling, tripping, control or protection functions according to the needs of the panel.
It can also be combined with compatible residual current protection solutions when the installation requires supplementary protection against leakage currents.
With its 4 A rating and D tripping characteristic, this miniature circuit breaker can be used to protect properly sized circuits with high inrush currents, including:
Suitability for each application should be verified by the corresponding protection calculation and by taking the load characteristics into account.
The Schneider Electric Acti9 iC60N A9F75204 provides bipolar protection against overloads and short circuits for 4 A circuits that require a D tripping curve. Its breaking capacity of 6 kA at 400 V according to IEC/EN 60898-1 and up to 50 kA according to IEC/EN 60947-2 makes it suitable for electrical panels with demanding protection requirements.
VisiTrip and VisiSafe technologies, its class 3 energy limiting, high mechanical and electrical durability, and compatibility with Acti9 accessories complete a modular solution designed for professional installations where reliable protection, easy maintenance and integration within the Schneider Electric Acti9 system are required.