The Schneider Electric A9F79332 is a thermal-magnetic miniature circuit breaker from the Acti9 iC60N range, designed to protect electrical circuits against overloads and short circuits. It features 3 protected poles, a rated current of 32 A and C tripping curve, offering a breaking capacity of 10 kA at 380-415 V AC according to IEC/EN 60947-2 and 6 kA at 400 V AC according to IEC/EN 60898-1.
Its thermal-magnetic tripping technology combines thermal protection against sustained overloads and fast magnetic operation in the event of short circuits. It also integrates Schneider Electric’s VisiTrip and VisiSafe technologies, which make it easier to identify trips and visually verify contact opening during maintenance tasks.
The Acti9 iC60N A9F79332 combines two protection principles. The thermal trip responds to prolonged overloads that could cause excessive heating of the conductors, while the magnetic trip acts quickly when a high short-circuit current occurs.
This combination makes it possible to use the circuit breaker as a line and load protection device in low-voltage electrical installations, provided that the rated current, conductor cross-section and load characteristics are compatible with its specifications.
The A9F79332 uses a C tripping curve. Schneider Electric specifies for this model a magnetic tripping threshold of approximately 8 times the rated current, with a tolerance of ±20%.
The C curve is widely used in distribution circuits with loads that may present moderate inrush currents, such as certain lighting installations, pumps and other compatible loads.
The breaking capacity of the circuit breaker depends on the operating voltage and the standard applied. At a mains voltage of 380-415 V AC, the Schneider Electric A9F79332 offers a ultimate breaking capacity Icu of 10 kA according to IEC/EN 60947-2.
Voltage Breaking capacity Standard 220-240 V AC 20 kA Icu IEC/EN 60947-2 380-415 V AC 10 kA Icu IEC/EN 60947-2 440 V AC 6 kA Icu IEC/EN 60947-2 400 V AC 6 kA Icn IEC/EN 60898-1For this reason, the commercial designation of 10 kA should be understood in reference to the breaking capacity established by IEC/EN 60947-2 at 380-415 V AC.
In addition to the ultimate breaking capacity Icu, Schneider Electric specifies the service breaking capacity Ics, which represents the breaker’s ability to continue operating after interrupting certain short-circuit currents within the conditions defined by the standard.
Voltage Ics 220-240 V AC 15 kA, 75% of Icu 380-415 V AC 7.5 kA, 75% of Icu 440 V AC 4.5 kA, 75% of IcuThe iC60N A9F79332 has 3 poles with thermal-magnetic protection on all three conductors. This configuration is especially suitable for three-phase circuits where simultaneous disconnection and protection of the three phases are required.
The device does not include a neutral pole, so a different configuration must be selected when the installation also requires isolation or protection of the neutral conductor.
The VisiTrip technology provides a front mechanical indication when the circuit breaker has tripped due to an electrical fault. This makes it easier to locate the affected circuit in panels containing numerous modular devices.
This indication can reduce the time needed to identify a tripped protection device during maintenance and troubleshooting tasks.
The VisiSafe system in the Acti9 range provides a visual indication through a green band when the contacts are physically open, making it easier to check the breaker status before carrying out downstream work.
The iC60N is also declared suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2.
The Schneider Electric A9F79332 has an energy limiting class 3 in accordance with IEC/EN 60898-1. The limiting capability reduces the energy let through by the breaker during a short circuit, helping to reduce thermal and electrodynamic stress on the downstream installation.
The circuit breaker is designed for fixed mounting on a DIN rail and occupies a total width of 54 mm, equivalent to 3 modules of 18 mm. This modular construction allows it to be installed alongside other Acti9 devices inside distribution electrical panels.
Electrical supply can be made from the top or bottom, facilitating different wiring configurations and the use of compatible distribution systems from the Acti9 range.
The terminals accept rigid and flexible conductors of different cross-sections. According to the product technical data, it accepts rigid conductors up to 35 mm² and flexible conductors up to 25 mm².
The cross-sections used and tightening torque must be selected following Schneider Electric’s official instructions and the electrical requirements of the circuit.
The breaker terminals have an IP20 protection rating in accordance with IEC/EN 60529. Once correctly installed in a modular panel with the appropriate enclosure, the assembly can achieve a higher front protection level depending on the characteristics of the panel used.
The Schneider Electric Acti9 iC60N A9F79332 is designed to operate in an ambient temperature range of -35 to +70 °C, allowing use in a wide variety of electrical panels and installations.
The iC60N can be complemented with different electrical auxiliaries and accessories from the Acti9 platform to add signaling, tripping or remote control functions.
It can also be complemented with compatible residual current blocks when earth leakage protection is required. The A9F79332 circuit breaker on its own does not include residual current protection.
The Schneider Electric A9F79332 is designed in accordance with IEC/EN 60898-1 and IEC/EN 60947-2, applicable to low-voltage circuit breakers and circuit protection devices.
The Schneider Electric Acti9 iC60N A9F79332 combines thermal-magnetic protection, 3 protected poles, a rated current of 32 A, C curve and a breaking capacity of 10 kA at 380-415 V according to IEC/EN 60947-2. Its VisiTrip and VisiSafe technologies, modular DIN rail mounting and compatibility with Acti9 auxiliaries make it a versatile solution for protecting three-phase circuits in residential, commercial and industrial electrical installations.