IC60N Circuit Breaker 3P 6A Curve C with reference A9F79306 from the brand SCHNEIDER ELECTRIC
IC60N Circuit Breaker 3P 6A Curve C with reference A9F79306 from the brand SCHNEIDER ELECTRIC
SCHNEIDER ELECTRIC

IC60N Circuit Breaker 3P 6A Curve C

REF
A9F79306
(0)
54.91 €
€54.91
€255.56
Up to -6% for professionals. Discover it.
Schneider Electric Acti9 iC60N 3P 6 A circuit breaker, C curve and 6 kA breaking capacity. Protects circuits against overloads and short circuits with VisiTrip and VisiSafe.
Buy now and receive it between 20 and November 23
Express delivery
Get +55 +110 Sumis for the purchase
Receive 2x Sumis for a limited time
More about the product

Information about IC60N Circuit Breaker 3P 6A Curve C

The Schneider Electric Acti9 iC60N A9F79306 miniature circuit breaker is a modular circuit breaker designed to protect electrical circuits against overloads and short circuits. It features 3 protected poles, a rated current of 6 A, and C tripping curve, providing a compact solution for distribution switchboards in residential, commercial, and professional installations.

Its thermal-magnetic trip unit combines thermal protection against prolonged overloads and fast magnetic tripping in the event of short circuits. The device offers a rated breaking capacity of 6000 A at 400 V AC according to IEC/EN 60898-1 and an Icu breaking capacity of 10 kA at 380-415 V AC according to IEC/EN 60947-2. It also incorporates the VisiTrip and VisiSafe technologies characteristic of the Acti9 range.

Three-phase 6 A miniature circuit breaker with C curve

Reference A9F79306 has a 3P configuration, with independent protection on all three poles. This arrangement makes it suitable for three-phase circuits where all three phases must be disconnected simultaneously in the event of an overload or short circuit.

Its rated current is 6 A and it uses a C tripping curve. Schneider Electric specifies a magnetic threshold of 8 times the rated current ±20% for this model, a feature suitable for many distribution circuits with moderate inrush currents.

Thermal and magnetic protection

The Acti9 iC60N uses thermal-magnetic tripping technology that combines two protection systems:

  • Thermal protection: acts when a current above the rated value persists for an extended period, preventing conductor overheating.
  • Magnetic protection: intervenes quickly when a high current caused by a short circuit occurs.

In this way, the A9F79306 protects wiring and downstream connected equipment against the main overcurrents that may occur during the operation of an electrical installation.

6 kA breaking capacity at 400 V

The Schneider Electric A9F79306 has a 6000 A Icn breaking capacity at 400 V AC according to IEC/EN 60898-1. According to IEC/EN 60947-2, the breaking capacity varies depending on the operating voltage:

  • 36 kA between 12 and 60 V AC.
  • 36 kA between 100 and 133 V AC.
  • 20 kA between 220 and 240 V AC.
  • 10 kA between 380 and 415 V AC.
  • 6 kA at 440 V AC.
  • 10 kA up to 180 V DC.

These performance ratings allow the miniature circuit breaker to be adapted to different network configurations, always respecting the voltages, breaking capacities, and installation conditions specified by Schneider Electric.

VisiTrip technology for trip identification

The miniature circuit breaker includes the VisiTrip system, designed to make diagnosis inside the electrical panel easier. When the circuit breaker trips due to an electrical fault, the indicator makes it possible to quickly identify the affected circuit.

This function is especially useful in panels with numerous devices, as it reduces the time needed to locate the tripped miniature circuit breaker and simplifies maintenance tasks.

VisiSafe for contact opening verification

The VisiSafe technology provides a visual indication of the device’s open state. The green band makes it possible to verify that the contacts are physically open, providing an additional reference for downstream maintenance operations.

The A9F79306 is also suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2.

Class 3 current limiting

This circuit breaker offers a Class 3 current limiting rating according to IEC/EN 60898-1. Limiting energy during a short circuit helps reduce the thermal and electrodynamic stresses on downstream conductors and equipment.

This feature contributes both to circuit protection and to improved coordination with other correctly sized electrical devices.

Compatible with AC and DC networks

The Schneider Electric Acti9 iC60N A9F79306 can operate on alternating current and direct current within the limits specified by the manufacturer.

  • AC frequency: 50/60 Hz.
  • Typical three-phase voltage: 400 V AC.
  • Breaking capacity at 380-415 V AC: 10 kA according to IEC/EN 60947-2.
  • DC breaking capacity: 10 kA up to 180 V DC according to IEC/EN 60947-2.

Modular DIN rail mounting

The miniature circuit breaker is designed for fixed installation on a DIN rail in modular electrical panels. Its three-pole format occupies 3 modules, allowing it to be combined with residual current devices, contactors, auxiliaries, and other Acti9 family devices.

  • Number of poles: 3.
  • Number of protected poles: 3.
  • Modular width: 3 modules.
  • Construction depth: 44.5 mm.
  • Mounting: fixed on DIN rail.

Conductor connection

The A9F79306 uses terminals designed to ensure a reliable connection inside the electrical panel. It accepts the following conductor sizes:

  • Rigid conductor: 1 to 25 mm².
  • Flexible conductor: 1 to 16 mm².
  • Strip length: 14 mm.

The Acti9 range also allows the use of different compatible distribution and connection accessories to simplify the assembly of multiple devices within the same enclosure.

Compatible with Acti9 auxiliaries

The miniature circuit breaker supports the addition of compatible auxiliary devices, making it possible to expand the functions of the electrical panel through signaling, remote tripping, monitoring, or other Acti9 platform solutions.

Residual current protection can be provided by a compatible independent residual current block, allowing overload and short-circuit protection to be combined with residual current protection when the installation design requires it.

IP20 protection

The device has an IP20 protection rating at its terminals according to IEC/EN 60529. Once correctly installed inside a suitable class II modular enclosure, it can achieve a higher front protection level depending on the panel configuration.

The operating ambient temperature range is -35 to 70 °C, allowing use in a wide variety of environmental conditions within the manufacturer’s specifications.

Technical characteristics of the Schneider Electric A9F79306

  • Brand: Schneider Electric.
  • Reference: A9F79306.
  • Range: Acti9.
  • Product: Acti9 iC60N.
  • Type: modular thermal-magnetic circuit breaker.
  • Application: electrical distribution.
  • Number of poles: 3P.
  • Protected poles: 3.
  • Rated current: 6 A.
  • Tripping curve: C.
  • Tripping technology: thermal-magnetic.
  • Magnetic threshold: 8 x In ±20%.
  • Network type: AC and DC.
  • Frequency: 50/60 Hz.
  • Operating voltage: 400 V AC.
  • Icn breaking capacity: 6 kA at 400 V AC according to IEC/EN 60898-1.
  • Icu breaking capacity: 20 kA at 220-240 V AC according to IEC/EN 60947-2.
  • Icu breaking capacity: 10 kA at 380-415 V AC according to IEC/EN 60947-2.
  • Icu breaking capacity: 6 kA at 440 V AC according to IEC/EN 60947-2.
  • DC breaking capacity: 10 kA up to 180 V DC.
  • Rated insulation voltage Ui: 500 V.
  • Impulse withstand voltage Uimp: 6 kV.
  • Utilization category: A.
  • Limiting class: 3.
  • Overvoltage category: IV.
  • Pollution degree: 3.
  • Suitable for isolation: yes.
  • Trip indicator: VisiTrip.
  • Open indication: VisiSafe.
  • Mounting: DIN rail.
  • Width: 3 modules.
  • Construction depth: 44.5 mm.
  • Protection rating: IP20.
  • Rigid conductor: 1-25 mm².
  • Flexible conductor: 1-16 mm².
  • Operating temperature: -35 to 70 °C.
  • Maximum operating altitude: 2000 m.
  • Power loss: approximately 1.3 W.
  • Standards: IEC/EN 60898-1 and IEC/EN 60947-2.
  • EAN: 3606480093302.

Three-phase protection for electrical panels

The Schneider Electric A9F79306 is designed to protect 6 A three-phase circuits in distribution switchboards. Its C curve provides suitable performance for many general-purpose circuits and loads with moderate inrush currents.

The combination of 3 protected poles, 6 A, C curve, 6 kA breaking capacity, Class 3 current limiting, and VisiTrip and VisiSafe technologies offers a complete solution for protecting circuits against overloads and short circuits while simplifying diagnosis and maintenance tasks.

Specifications
Manufacturer
SCHNEIDER ELECTRIC
Reference
A9F79306
SKU
SCH9535DC8D
Object
Magnetic circuit breaker
Number of poles
Assembly
Fixed
Nominal current
6 A
Network type
CA, CC
Protection rating
IP20
Frequency
50.00 - 60.00 Hz
Datasheets
Reviews
Returns within 30 days
Shop with peace of mind. If something goes wrong, we'll take care of it.
After-sales service
Any questions? Our support team will be happy to help you.
Pay how and when you want
Card, bank transfer, PayPal... Installment? We have them all.
GroupSumi is your online distributor for construction, electrical material and climate control.
All rights reserved © 2026 GroupSumi