The Schneider Electric Acti9 iC60N A9F79306 miniature circuit breaker is a modular circuit breaker designed to protect electrical circuits against overloads and short circuits. It features 3 protected poles, a rated current of 6 A, and C tripping curve, providing a compact solution for distribution switchboards in residential, commercial, and professional installations.
Its thermal-magnetic trip unit combines thermal protection against prolonged overloads and fast magnetic tripping in the event of short circuits. The device offers a rated breaking capacity of 6000 A at 400 V AC according to IEC/EN 60898-1 and an Icu breaking capacity of 10 kA at 380-415 V AC according to IEC/EN 60947-2. It also incorporates the VisiTrip and VisiSafe technologies characteristic of the Acti9 range.
Reference A9F79306 has a 3P configuration, with independent protection on all three poles. This arrangement makes it suitable for three-phase circuits where all three phases must be disconnected simultaneously in the event of an overload or short circuit.
Its rated current is 6 A and it uses a C tripping curve. Schneider Electric specifies a magnetic threshold of 8 times the rated current ±20% for this model, a feature suitable for many distribution circuits with moderate inrush currents.
The Acti9 iC60N uses thermal-magnetic tripping technology that combines two protection systems:
In this way, the A9F79306 protects wiring and downstream connected equipment against the main overcurrents that may occur during the operation of an electrical installation.
The Schneider Electric A9F79306 has a 6000 A Icn breaking capacity at 400 V AC according to IEC/EN 60898-1. According to IEC/EN 60947-2, the breaking capacity varies depending on the operating voltage:
These performance ratings allow the miniature circuit breaker to be adapted to different network configurations, always respecting the voltages, breaking capacities, and installation conditions specified by Schneider Electric.
The miniature circuit breaker includes the VisiTrip system, designed to make diagnosis inside the electrical panel easier. When the circuit breaker trips due to an electrical fault, the indicator makes it possible to quickly identify the affected circuit.
This function is especially useful in panels with numerous devices, as it reduces the time needed to locate the tripped miniature circuit breaker and simplifies maintenance tasks.
The VisiSafe technology provides a visual indication of the device’s open state. The green band makes it possible to verify that the contacts are physically open, providing an additional reference for downstream maintenance operations.
The A9F79306 is also suitable for isolation according to IEC/EN 60898-1 and IEC/EN 60947-2.
This circuit breaker offers a Class 3 current limiting rating according to IEC/EN 60898-1. Limiting energy during a short circuit helps reduce the thermal and electrodynamic stresses on downstream conductors and equipment.
This feature contributes both to circuit protection and to improved coordination with other correctly sized electrical devices.
The Schneider Electric Acti9 iC60N A9F79306 can operate on alternating current and direct current within the limits specified by the manufacturer.
The miniature circuit breaker is designed for fixed installation on a DIN rail in modular electrical panels. Its three-pole format occupies 3 modules, allowing it to be combined with residual current devices, contactors, auxiliaries, and other Acti9 family devices.
The A9F79306 uses terminals designed to ensure a reliable connection inside the electrical panel. It accepts the following conductor sizes:
The Acti9 range also allows the use of different compatible distribution and connection accessories to simplify the assembly of multiple devices within the same enclosure.
The miniature circuit breaker supports the addition of compatible auxiliary devices, making it possible to expand the functions of the electrical panel through signaling, remote tripping, monitoring, or other Acti9 platform solutions.
Residual current protection can be provided by a compatible independent residual current block, allowing overload and short-circuit protection to be combined with residual current protection when the installation design requires it.
The device has an IP20 protection rating at its terminals according to IEC/EN 60529. Once correctly installed inside a suitable class II modular enclosure, it can achieve a higher front protection level depending on the panel configuration.
The operating ambient temperature range is -35 to 70 °C, allowing use in a wide variety of environmental conditions within the manufacturer’s specifications.
The Schneider Electric A9F79306 is designed to protect 6 A three-phase circuits in distribution switchboards. Its C curve provides suitable performance for many general-purpose circuits and loads with moderate inrush currents.
The combination of 3 protected poles, 6 A, C curve, 6 kA breaking capacity, Class 3 current limiting, and VisiTrip and VisiSafe technologies offers a complete solution for protecting circuits against overloads and short circuits while simplifying diagnosis and maintenance tasks.