The Schneider Electric A9F78416 is a thermal-magnetic circuit breaker from the Acti9 iC60N range, designed to protect electrical circuits against overloads and short circuits. It features 4 protected poles, a rated current of 16 A, and B tripping curve, with an Icu breaking capacity of 10 kA at 380-415 V AC according to IEC/EN 60947-2 and an Icn breaking capacity of 6 kA at 400 V AC according to IEC/EN 60898-1.
Its thermal-magnetic tripping technology combines thermal protection against prolonged overloads with fast magnetic operation in the event of short circuits. It also incorporates Schneider Electric’s VisiTrip and VisiSafe technologies, which respectively make it easier to identify tripped circuits and visually verify the safe opening of the contacts.
The A9F78416 incorporates thermal-magnetic protection on all four poles, allowing the four conductors connected to the device to be protected and disconnected simultaneously. This configuration is especially suitable for distribution circuits where four-pole protection is required.
The thermal part of the mechanism responds to sustained overloads that can cause excessive heating of the conductors, while the magnetic trip unit acts quickly against high short-circuit currents.
This model uses a B curve, with a magnetic operating threshold specified by Schneider Electric of 4 times the rated current with a tolerance of ±20 %.
The B curve has a more sensitive magnetic response than a C curve and is especially suited to circuits with low or moderate inrush currents. It can be used, for example, in certain distribution circuits, lighting circuits, and resistive loads, provided the curve is suitable for the actual electrical characteristics of the installation.
The breaking capacity of the Acti9 iC60N depends on the operating voltage and the applicable standard. At a voltage of 380-415 V AC, the A9F78416 provides an ultimate breaking capacity Icu of 10 kA in accordance with IEC/EN 60947-2.
Voltage Breaking capacity Standard 220-240 V AC 20 kA Icu IEC/EN 60947-2 380-415 V AC 10 kA Icu IEC/EN 60947-2 440 V AC 6 kA Icu IEC/EN 60947-2 400 V AC 6 kA Icn IEC/EN 60898-1Therefore, to correctly identify this circuit breaker, it is important to distinguish between the 10 kA according to IEC/EN 60947-2 and the 6 kA according to IEC/EN 60898-1.
The VisiTrip technology provides a front indication that makes it easy to identify when the circuit breaker has tripped due to an electrical fault. This function is especially useful in panels with numerous circuits, as it helps quickly locate the protection device that has operated.
This makes fault diagnosis easier and reduces the time needed to identify the affected circuit.
The VisiSafe system provides a visual indication that allows you to verify that the contacts are physically open. The circuit breaker is also declared suitable for isolation in accordance with IEC/EN 60898-1 and IEC/EN 60947-2.
This feature is especially useful during inspection and maintenance work on the electrical installation.
The Schneider Electric A9F78416 has energy limiting class 3. This feature helps reduce the energy passing through the installation during a short circuit, lowering the thermal and electrodynamic stresses on downstream conductors and equipment.
The Acti9 iC60N A9F78416 is designed for fixed installation on a DIN rail. Its four poles occupy a total width of 72 mm, equivalent to 4 DIN modules of 18 mm.
This format makes it easy to integrate with other Schneider Electric modular devices, such as residual current devices, contactors, control auxiliaries, and signaling elements within distribution switchboards.
As it is rated at 25 A or less, the iC60N accepts rigid copper conductors up to 25 mm² and flexible conductors up to 16 mm².
Conductor type Permitted cross-section Rigid conductor 1 to 25 mm² Flexible conductor 1 to 16 mm² Tightening torque 2 NmThe Schneider Electric A9F78416 is designed to operate at ambient temperatures between -35 and +70 °C, allowing it to be used in a wide variety of electrical panels and installations.
The device also has pollution degree 3 and overvoltage category IV according to its technical characteristics.
The iC60N allows different electrical auxiliaries and Acti9 accessories to be added to expand its functions. Schneider Electric options include signaling devices, remote trip units, and monitoring accessories.
It can also be combined with a compatible Vigi residual current protection unit when residual current detection is required. The A9F78416 on its own is a circuit breaker and does not include integrated residual current protection.
The Schneider Electric Acti9 iC60N A9F78416 is suitable for four-pole circuits up to 16 A where a B tripping curve and protection against overloads and short circuits are required.
The Schneider Electric A9F78416 thermal-magnetic circuit breaker complies with IEC/EN 60898-1 and IEC/EN 60947-2 standards applicable to low-voltage circuit breakers intended to protect circuits against overcurrents.
The Schneider Electric A9F78416 Acti9 iC60N combines four protected poles, 16 A, B curve, thermal-magnetic protection, and a 10 kA breaking capacity according to IEC/EN 60947-2. Its VisiTrip and VisiSafe technologies, modular format, and compatibility with Acti9 auxiliaries provide a complete solution for low-voltage electrical circuit protection.