The Schneider Electric Acti9 iK60N A9K17316 circuit breaker is a modular 3-pole, 16 A, C-curve automatic breaker designed to protect AC electrical circuits against overloads and short circuits. It features thermal-magnetic protection on all three poles and offers a rated breaking capacity Icn of 6 kA at 230 V AC according to EN/IEC 60898-1, making it a suitable solution for residential and tertiary distribution boards.
It is part of Schneider Electric’s Acti9 iK60 range and combines protection, control and isolation in a compact DIN rail device. Its C tripping curve has a magnetic threshold between 5 and 10 times the rated current, suitable for circuits with moderate inrush currents.
The A9K17316 has three poles, all of them protected by thermal-magnetic trip units. In the event of an overload, short circuit or manual operation, the mechanism opens all three phases simultaneously.
This configuration is especially suitable for three-phase circuits where all three phase conductors must be protected simultaneously by a single modular device.
The breaker combines two protection principles. The thermal element acts against sustained overloads that could cause excessive heating of conductors and equipment, while the magnetic mechanism responds quickly to the high currents produced by a short circuit.
This combination helps protect the installation against the main overcurrent situations, provided that the breaker rating and conductor cross-section are correctly sized.
The Schneider Electric A9K17316 uses a C tripping curve. The manufacturer specifies a magnetic operating threshold between 5 and 10 times the rated current.
The C curve can withstand certain transient current surges without nuisance tripping, which is why it is commonly used in general distribution circuits, lighting and other loads with moderate inrush currents.
The Acti9 iK60N A9K17316 offers a rated breaking capacity Icn of 6000 A at 230 V AC and 50/60 Hz in accordance with EN/IEC 60898-1.
Its service breaking capacity Ics also reaches 6000 A, equivalent to 100% of Icn under the conditions specified by Schneider Electric.
The selected breaking capacity must be equal to or greater than the prospective short-circuit current at the installation point.
The circuit breaker has a limiting class 3 according to EN/IEC 60898-1. This feature indicates a high ability to limit the energy flowing through the circuit during a short circuit.
Current limiting helps reduce the thermal and electrodynamic stresses on downstream conductors and equipment.
Schneider Electric declares the A9K17316 as suitable for isolation according to EN/IEC 60898-1. This allows the breaker to be used to isolate the circuit within the conditions defined by the standard and the manufacturer.
The front includes a handle and a local ON/OFF indication, making it easy to identify the device status.
The rated insulation voltage Ui is 440 V AC at 50/60 Hz, while the impulse withstand voltage Uimp reaches 4 kV.
These characteristics define the dielectric performance of the device with respect to continuous insulation voltage and certain transient overvoltages.
The A9K17316 is installed by clip-on mounting on a DIN rail and occupies 6 modules of 9 mm, equivalent to three standard 18 mm modules.
Its modular format allows it to be installed alongside residual current devices, contactors and other protection and control devices inside conventional electrical panels.
The Acti9 iK60N design incorporates a double fixing clip that makes it easier to remove the breaker from the DIN rail even when a comb busbar is installed.
This feature simplifies replacement and maintenance operations in panels with comb busbar distribution.
The breaker has tunnel terminals with top or bottom connection. Schneider Electric specifies the following capacities:
The final cross-section must be selected according to the design current, installation method, temperature, voltage drop and applicable electrical regulations.
Schneider Electric specifies a high service life for the iK60N:
These ratings allow the breaker to be used for a high number of operations within the conditions specified by the manufacturer.
The device has an IP20 protection rating according to IEC 60529. Once installed inside a suitable modular enclosure, the assembly can provide a higher level of protection depending on the characteristics of the panel used.
Schneider Electric also specifies a pollution degree 2 and overvoltage category III in the technical documentation available for this reference.
The circuit breaker is designed to operate within a wide ambient range:
In installations subject to high temperatures or significant grouping of devices, the thermal behavior of the assembly should be checked and Schneider Electric recommendations applied where appropriate.
The Acti9 iK60N supports the use of a compatible padlock locking device. This option allows the handle to be locked when it is necessary to prevent unauthorized operation during maintenance or circuit intervention.
The A9K17316 provides thermal-magnetic protection against overloads and short circuits, but it does not include residual current protection against earth leakage currents.
When the installation requires residual current protection, it must be combined with a suitable device selected according to the number of poles, sensitivity, class and circuit characteristics.
Due to its three-pole configuration, 16 A rating and C curve, this circuit breaker is suitable for applications such as:
The Schneider Electric A9K17316 combines three protected poles, a rated current of 16 A, C curve and 6 kA breaking capacity in a modular device only 54 mm wide. Its thermal-magnetic unit protects against overloads and short circuits, while limiting class 3 and suitability for isolation complete its features.
Its DIN rail mounting, double clip for easier removal, terminals for rigid conductors up to 25 mm² and durability of up to 20,000 mechanical cycles make it easy to integrate into professional distribution boards.
To ensure proper protection, the rating must be selected taking into account the expected current, conductor cross-section and capacity, available short-circuit current and the actual installation conditions.