The Schneider Electric Acti9 iK60N A9K24450 thermal-magnetic circuit breaker is a modular automatic switch with 4 protected poles, 50 A and C curve, designed to protect electrical circuits against overloads and short circuits. It offers a rated breaking capacity Icn of 6 kA at 400 V AC in accordance with EN/IEC 60898-1 and uses a thermal-magnetic tripping system, combining thermal protection against prolonged overloads and fast magnetic tripping against high short-circuit currents.
The A9K24450 reference is part of Schneider Electric's Acti9 iK60N range and is intended for low-voltage electrical distribution. Its four-pole configuration allows the four conductors connected to the device to be protected simultaneously, while DIN rail mounting, its modular format and possible top or bottom supply make it easy to integrate into residential, commercial and tertiary electrical panels.
The Schneider Electric A9K24450 has 4 total poles and 4 protected poles. Unlike a 3P+N configuration, where only the three phases include overcurrent protection, in this model all four poles are protected.
The Acti9 iK60N incorporates two complementary tripping principles:
This combination makes it possible to use a single device to protect wiring and the circuit against the main risks derived from overcurrent.
The A9K24450 reference uses a C curve. Schneider Electric specifies a magnetic tripping threshold between 5 and 10 times the rated current.
The C curve is one of the most widely used in electrical distribution and is suitable, provided the installation calculations allow it, for loads that may present moderate inrush currents.
It can be used in circuits such as:
Schneider Electric specifies for this model a rated breaking capacity Icn of 6,000 A at 400 V AC in accordance with EN/IEC 60898-1.
The breaking capacity indicates the maximum short-circuit current that the circuit breaker can interrupt under the conditions established by the standard. Therefore, before installing the thermal-magnetic breaker, it is necessary to check that the expected short-circuit current at the installation point does not exceed the device's capacity.
The A9K24450 has a service breaking capacity Ics of 6 kA at 400 V AC, equivalent to 100% of its Icn under the conditions established by EN/IEC 60898-1.
The Schneider Electric iK60N has limiting class 3 in accordance with EN/IEC 60898-1.
During a short circuit, current limiting helps reduce the energy that passes through the circuit before the breaker completes disconnection, reducing the thermal and electrodynamic stresses borne by conductors and equipment.
The main electrical characteristics of the A9K24450 are:
The A9K24450 is declared suitable for isolation or disconnection in accordance with EN/IEC 60898-1.
This feature allows it to be used to electrically isolate the circuit within the maintenance and safety procedures предусмотрed for the installation.
The Acti9 iK60 range incorporates a Fast Closing mechanism, designed so that the closing speed of the contacts is independent of how quickly the user operates the lever.
This operation provides consistent contact switching and helps improve the device's durability.
The thermal-magnetic breaker has local ON/OFF indication, allowing the lever position and the switching status of the breaker to be visually identified.
The reference does not include an independent physical contact position indicator or VisiTrip signaling like that available in other higher-performance Acti9 families.
The Schneider Electric A9K24450 is designed to be installed by clip-on mounting on a DIN rail.
The double-clip system makes it easier to remove the device even when a compatible distribution comb is installed.
Its modular format makes it possible to integrate four-pole protection while occupying four standard modules inside the electrical panel.
Schneider Electric allows the thermal-magnetic breaker to be supplied and connected from the top or bottom, providing flexibility during panel design and wiring.
The tunnel terminals accept:
To obtain a safe connection, it is necessary to respect the cable cross-sections, conductor preparation and tightening torque specified by the manufacturer.
The Acti9 iK60N is designed to provide a long service life in distribution panels.
These features allow the usual switching operations to be carried out throughout the service life of the equipment.
The A9K24450 has an IP20 protection rating as an individual device in accordance with IEC 60529.
Once correctly installed inside a suitable modular enclosure, the protection rating of the assembly can reach IP40 under the conditions indicated by Schneider Electric.
The rated current is specified at a reference temperature of 30 °C. In installations with different temperatures, the operating conditions and corresponding correction factors must be taken into account.
Due to its four-pole configuration, 50 A rating and C curve, this thermal-magnetic breaker can be used in numerous distribution circuits compatible with its electrical characteristics:
The A9K24450 is an MCB thermal-magnetic circuit breaker and its function is to protect against overloads and short circuits.
It does not include residual current protection against earth leakage. When the installation requires residual current protection, an appropriate residual current device must be used together with the circuit breaker.
The Schneider Electric Acti9 iK60N A9K24450 combines four protected poles, a 50 A rating, C curve and 6 kA breaking capacity at 400 V in a four-module format. Its thermal-magnetic protection, class 3 current limiting and suitability for isolation make it suitable as main protection or for outgoing circuits when its characteristics are compatible with the electrical design.
The Fast Closing mechanism, double fixing clip, top or bottom supply and durability of up to 20,000 mechanical cycles complete a practical solution for residential, commercial and tertiary distribution panels.
Important: before installing the A9K24450, the circuit design current, conductor cross-section, C curve, expected short-circuit current and required breaking capacity must be checked. The device does not include residual current protection and, when this is required, it must be complemented with a correctly selected residual current device.