The Schneider Electric Acti9 NG125N 18654 thermal-magnetic circuit breaker is a low-voltage automatic switch with 4 protected poles, 40 A and C curve, designed to protect electrical circuits against overloads and short circuits. It offers a high ultimate breaking capacity Icu of 25 kA at 380-415 V AC in accordance with IEC/EN 60947-2, making it a particularly suitable solution for professional distribution boards where short-circuit levels may be higher than those typically found in domestic installations.
The 18654 reference belongs to Schneider Electric's Acti9 NG125N range and combines thermal-magnetic protection, four protected poles, isolating capability, mechanical trip indication and DIN rail mounting. In addition, it supports the addition of auxiliaries and compatible Vigi NG125 residual current blocks to expand the protection, control and signalling functions of the assembly.
The Schneider Electric 18654 features 4 total poles and 4 protected poles. Each pole includes overcurrent protection and all four contacts operate simultaneously.
This configuration is suitable for circuits where protection is required on all four conductors connected to the breaker.
The Acti9 NG125N uses a thermal-magnetic trip system that integrates two complementary mechanisms:
In this way, the device protects the circuit against the main types of overcurrent with a single circuit breaker.
Reference 18654 incorporates a C curve. Schneider Electric specifies for the NG125N a magnetic trip threshold of 8 times the rated current.
In this 40 A model, this feature allows certain transient inrush currents to be tolerated without immediate magnetic tripping, while still maintaining fast operation in the event of short circuits.
The curve should be selected taking into account the nature of the load, starting currents and the available fault current at the installation point.
One of the most notable features of the Schneider Electric NG125N 18654 is its high interrupting capacity.
According to IEC/EN 60947-2, Schneider Electric specifies the following ultimate breaking capacity Icu values in AC:
In typical 400 V three-phase networks, the reference value is therefore an Icu of 25 kA.
The service breaking capacity also varies depending on the operating voltage. Schneider Electric specifies:
Before selecting the circuit breaker, its breaking capacity must be checked to ensure it is equal to or greater than the prospective short-circuit current at the installation point.
The NG125N range is specified for applications in both alternating current and certain direct current networks.
In AC, the device has operating characteristics for voltages of:
Schneider Electric also provides for DC applications with specific configurations and breaking capacities. In these cases, the number of poles, voltage and connection scheme indicated by the manufacturer must be strictly respected.
The Acti9 NG125N 18654 is suitable for isolation or disconnection in accordance with IEC/EN 60947-2.
This feature allows the device to be used as a circuit disconnection element during maintenance tasks, always applying the corresponding safety and lockout procedures.
The front includes a red mechanical trip indicator that makes it possible to visually distinguish an operation caused by an electrical fault.
It also has ON/OFF position indication, making it easy to quickly identify the breaker status inside the panel.
The NG125N includes a manual trip test function, intended to check the mechanical operation of the breaker during the corresponding maintenance operations.
Among the main dielectric characteristics of the device are:
These features allow the NG125N to be used in distribution boards with requirements higher than those of small conventional domestic circuit breakers.
The Schneider Electric 18654 is installed by clip-on mounting on a 35 mm symmetrical DIN rail.
This solution makes it easy to integrate it alongside other protection, control and electrical distribution devices inside the enclosure.
The breaker has the following dimensions:
Its size is larger than that of conventional modular circuit breakers, in line with its breaking capacity and electrical performance.
The NG125N incorporates tunnel terminals capable of accepting conductors of:
The final cross-section must be selected according to the circuit current, installation method and applicable regulations.
The Schneider Electric Acti9 NG125N allows different accessories to be added to expand the device's functions.
Depending on the configuration, it can be combined with:
The 18654 is a thermal-magnetic circuit breaker and on its own protects against overloads and short circuits, but does not include residual current earth leakage detection.
Schneider Electric provides for the addition of a compatible Vigi NG125 residual current block when the installation requires residual current protection.
The mechanical and protection characteristics include:
The breaker must be installed inside a suitable enclosure that provides the degree of protection required by the environment.
The Schneider Electric 18654 is designed to operate in:
Its wide thermal range makes it suitable for use in many professional distribution boards within the conditions established by the manufacturer.
Schneider Electric specifies for the currently documented version:
These features provide a long service life when the breaker operates within its rated limits.
With its 40 A rated current, four protected poles and 25 kA breaking capacity at 400 V, it can be used in panels where the short-circuit level is high and four-pole protection is required.
Possible applications include:
The Schneider Electric Acti9 NG125N 18654 combines a 40 A rated current, four protected poles and C curve with a high breaking capacity of 25 kA at 380-415 V. These features make it a particularly suitable solution for professional panels where the expected short-circuit current requires performance above that of conventional modular circuit breakers.
Its mechanical trip indication, suitability for isolation, terminals for conductors up to 50 mm² rigid and compatibility with auxiliaries and Vigi NG125 blocks make it easy to integrate into complete electrical distribution systems.
Important: the 18654 is a thermal-magnetic circuit breaker and does not include residual current protection. Before installation, the 40 A rating, conductor cross-section, C curve, expected short-circuit current and required breaking capacity must be verified. When protection against earth leakage is required, it must be complemented with a properly sized compatible residual current solution.