The Schneider Electric TeSys Deca LC1D12V7 contactor is a three-pole contactor designed for controlling electric motors and resistive loads in automation panels, machinery, and industrial installations. It features 3 normally open main contacts, a rated current of 12 A in AC-3 and AC-3e categories up to 440 V, and a 400 V AC control coil at 50/60 Hz. It also includes as standard 1 NO auxiliary contact + 1 NC auxiliary contact.
In three-phase 380-400 V networks, it can control motors up to 5.5 kW in AC-3/AC-3e category. Its compact design, DIN rail or panel mounting, high mechanical durability, and compatibility with TeSys accessories make it ideal for pumps, fans, compressors, HVAC systems, machinery, and control panels.
The LC1D12V7 has three normally open power poles. When the coil is energized, the three main contacts close simultaneously to supply the connected motor or load.
Schneider Electric specifies a rated current of 12 A in AC-3 and AC-3e up to 440 V, categories mainly intended for controlling squirrel-cage motors.
The maximum motor power depends on the supply voltage. Schneider Electric specifies for this contactor:
In a typical 400 V three-phase network, this reference is therefore suitable for motors up to 5.5 kW, provided the actual current and duty cycle are compatible.
The V7 suffix identifies this version with a 400 V AC control coil compatible with 50 and 60 Hz. When the coil is energized, the contactor closes; when the control voltage is removed, the contacts return to their rest position.
The coil does not include an integrated suppression module, although the contactor accepts compatible TeSys accessories when the application requires limiting overvoltages generated during switching off.
In addition to the three main power contacts, the LC1D12V7 includes:
These contacts can be used for self-holding, signaling, interlocking, feedback to PLCs, or controlling other circuit elements.
The NO and NC auxiliary contacts are mechanically linked in accordance with IEC 60947-5-1, and the NC contact has a mirror contact function in accordance with IEC 60947-4-1.
The contactor capacity varies depending on the type of load:
The 12 A rating is mainly for motor control, while the 25 A AC-1 rating applies to non-inductive or slightly inductive loads. Selection should always be made according to the actual utilization category.
The main circuit can be used with a rated operational voltage of up to 690 V AC, between 25 and 400 Hz. Schneider Electric also covers certain DC applications up to 300 V.
The rated insulation voltage is 690 V according to IEC 60947 and the impulse withstand voltage Uimp is 6 kV. The device belongs to overvoltage category III.
Schneider Electric specifies the following conventional free-air thermal currents at 60 °C:
The main circuit has a rated making capacity of 250 A at 440 V in accordance with IEC 60947.
The rated breaking capacity also reaches 250 A at 440 V.
For the power circuit, Schneider Electric specifies:
These ratings do not replace short-circuit protection devices, which must be coordinated with the contactor.
Schneider Electric specifies the following coordination references:
Final protection must be selected taking into account the motor, starting scheme, and Schneider Electric coordination tables.
The LC1D12V7 is designed for applications with a high number of switching operations:
The coil has a high consumption only during pull-in and a considerably lower consumption during holding:
These short times allow the contactor to be integrated into automation and switching panels with fast response.
The Schneider Electric LC1D12V7 can be installed on a DIN rail or mounted on a panel, offering flexibility for distribution boards, control panels, and machinery.
The LC1D12V7 reference uses screw terminals for both power and control.
Schneider Electric allows, depending on the number and type of conductor:
The contactor has reduced dimensions that make installation easier in space-limited panels:
The front of the contactor offers an IP20 protection rating in accordance with IEC 60529. It must be installed inside a suitable enclosure or cabinet to achieve the protection level required by the application.
The LC1D12V7 can be combined with TeSys range accessories to create complete control and protection solutions, including:
Thanks to its 12 A rating and 400 V AC coil, this contactor can be used in applications such as:
The TeSys Deca LC1D12V7 is designed in accordance with international standards for contactors and control devices, including:
The Schneider Electric LC1D12V7 combines a rated current of 12 A in AC-3/AC-3e, motor capacity up to 5.5 kW at 400 V, and a 400 V AC control coil at 50/60 Hz. The three NO main contacts switch the power circuit, while the 1 NO + 1 NC auxiliaries enable signaling, interlocking, and automation functions.
Its compact 45 mm width, DIN rail or panel mounting, up to 15 million mechanical cycles, and compatibility with TeSys accessories make this reference a versatile solution for machinery, pumps, fans, compressors, and industrial control panels.