The Schneider Electric TeSys Deca LC1D18P7 contactor is a power electromagnetic contactor designed for motor control and resistive loads. It features 3 poles with 3 normally open main contacts, a rated operational current of 18 A in AC-3 and AC-3e categories up to 440 V, and a 230 V AC control coil at 50/60 Hz. In motor applications, it can control up to 7.5 kW at 380-400 V and includes as standard 1 NO auxiliary contact + 1 NC auxiliary contact.
The LC1D18P7 reference belongs to the TeSys Deca family, traditionally also marketed as TeSys D, and is intended for industrial applications, machinery, and HVAC systems. Its compact 45 mm width, screw terminals, and the option for DIN rail or panel mounting make it easy to integrate into motor starters and automation panels.
The LC1D18P7 incorporates 3 normally open main contacts designed to connect and disconnect the three phases of a three-phase load simultaneously.
In AC-3/AC-3e category, Schneider Electric specifies a rated operational current of 18 A up to 440 V AC, within the contactor’s rated conditions.
AC-3 is especially associated with starting and stopping squirrel-cage asynchronous motors, where the contactor withstands inrush current during closing and opens when the motor is running under normal conditions.
The permissible motor power depends on the supply voltage. Schneider Electric specifies for this reference:
On a typical 400 V three-phase network, the LC1D18P7 can therefore control motors up to 7.5 kW in AC-3, provided the motor rated current and starting conditions are compatible.
The suffix P7 identifies the version equipped with a 230 V AC control coil at 50/60 Hz.
The coil allows the contactor to be controlled by devices such as pushbuttons, relays, pressure switches, thermostats, limit switches, automation systems, or compatible controllers.
When the coil is energized, the electromagnetic mechanism closes the three main contacts. When control power is removed, the contacts return to their open position.
In addition to the three power main contacts, the LC1D18P7 integrates:
Therefore, the correct contactor composition is:
The auxiliary contacts can be used for self-holding, signaling, feedback to a PLC, electrical interlocking, or automation sequences.
Schneider Electric specifies that the 1 NO + 1 NC auxiliary contacts are mechanically linked in accordance with IEC 60947-5-1.
The normally closed contact also includes a mirror contact characteristic in accordance with IEC 60947-4-1, useful in certain monitoring systems when the complete electrical scheme has been designed to take advantage of this function.
In addition to motor control, the LC1D18P7 can be used for certain resistive or slightly inductive loads.
In AC-1 category, Schneider Electric specifies a rated operational current of up to 32 A at voltages up to 440 V.
This value should not be confused with the 18 A in AC-3, since AC-1 and AC-3 correspond to different load types and switching conditions.
The contactor can be used in different utilization categories depending on the load:
For AC-4 applications at 400 V, Schneider Electric specifies a motor power of approximately 4 kW.
The LC1D18P7 main circuit supports:
The specific electrical characteristics must always be checked according to the utilization category, voltage, and connected load.
The LC1D18P7 reference uses screw terminals for the power circuit and control circuit, providing a conventional and robust connection inside the electrical panel.
The specified tightening torque for the main and control terminals is approximately 1.7 Nm, depending on the conductor and tool used.
The contactor can be installed by:
This flexibility makes it suitable for both small automation panels and larger industrial enclosures.
The Schneider Electric LC1D18P7 has compact dimensions:
The width of only 45 mm allows several contactors to be installed in limited spaces and facilitates the creation of compact starters.
The TeSys Deca LC1D18P7 is designed to withstand a high number of operations:
The standard AC coil has approximately:
The coil does not include an integrated surge suppression module as standard. When required by the application, compatible suppression accessories from the TeSys range can be used.
Schneider Electric specifies approximate switching times of:
These times allow the contactor to be integrated into automation systems with fast and repetitive sequences.
The front face of the LC1D18P7 has an IP20 protection rating in accordance with IEC 60529.
The contactor is designed to be installed inside an enclosure or electrical cabinet that provides the required protection against the environment and access to live parts.
The specified environmental conditions for the contactor include:
The contactor can be properly sized and integrated into applications such as:
The LC1D18P7 is part of the TeSys platform and can be combined with different compatible accessories, such as:
The reference for each accessory should be checked according to the required current, voltage, function, and coordination.
The Schneider Electric TeSys Deca LC1D18P7 combines an AC-3/AC-3e current rating of 18 A, motor capacity up to 7.5 kW at 400 V, and a 230 V AC coil in a compact 45 mm-wide format. The integrated 1 NO + 1 NC auxiliary contacts make it easy to create interlocking and signaling circuits.
Its high mechanical durability, screw terminals, DIN rail or panel mounting, and the wide range of TeSys accessories make it easy to integrate into panels for machinery, pumps, fans, compressors, and HVAC systems.
Important: the LC1D18P7 is a switching and control device and does not itself provide overload or short-circuit protection. In motor applications, it must be combined with a motor protection switch, thermal overload relay, fuses, or a circuit breaker correctly sized for the characteristics of the motor and installation.