The Schneider Electric TeSys D LC1D18BL contactor is a three-pole electromechanical contactor designed for motor control and resistive loads in electrical panels, machinery, and automation systems. It features 3 normally open main contacts (3 NO), a rated operational current of 18 A in AC-3 category up to 440 V, and a low-consumption 24 V DC control coil.
The LC1D18BL reference also includes 1 NO auxiliary contact + 1 NC auxiliary contact and an integrated bidirectional surge suppressor in the coil, reducing overvoltages generated when the control circuit is switched off. For three-phase motors, it offers power up to 7.5 kW at 380-400 V AC.
The Schneider Electric LC1D18BL is mainly intended for motor control and resistive loads. Its main circuit has three normally open poles that switch together when the coil is energized.
One of the main features of the LC1D18BL reference is its low-consumption 24 V DC coil. This configuration is especially suitable for control circuits powered from 24 V DC supplies, PLCs, interface relays, and automation systems.
The coil incorporates a bidirectional peak-limiting suppressor. This element helps limit transient overvoltages generated when the coil is de-energized, reducing disturbances that could affect other components in the control circuit.
This feature explains the common commercial designation of suppressed low-consumption coil associated with this reference.
In addition to the three main power contacts, the contactor includes from the factory one normally open auxiliary contact and one normally closed auxiliary contact.
These contacts can be used for self-holding, signaling, interlocking, status feedback, or communication with automation systems.
In AC-3 category, intended for standard squirrel-cage motor control, Schneider Electric specifies different maximum power ratings depending on the supply voltage:
In AC-4 category, for more demanding switching applications, Schneider Electric specifies 4 kW at 400 V AC.
The main circuit supports a rated operational voltage of up to 690 V AC between 25 and 400 Hz. It also supports DC operation up to 300 V DC within the conditions indicated by Schneider Electric.
The LC1D18BL has a rated making capacity of 300 A at 440 V in the power circuit according to IEC 60947. Its rated breaking capacity is also 300 A at 440 V.
For type 2 coordination, Schneider Electric indicates an associated 35 A gG fuse up to 690 V. For type 1 coordination, the indicated value is 50 A gG.
The contactor is designed for applications with a high number of operations and achieves a mechanical durability of up to 30 million cycles.
The low-consumption coil has operating times suited to automation and control systems:
The Schneider Electric LC1D18BL offers installation flexibility and can be mounted on either DIN rail or panel. This makes it easy to integrate into automation panels, motor starters, and industrial electrical assemblies.
The power circuit and control circuit use screw terminals, compatible with rigid and flexible conductors in different cross-sections.
The contactor has an IP20 front protection rating according to IEC 60529 and is designed to be installed inside a suitable enclosure or electrical panel.
The Schneider Electric LC1D18BL complies with the main international standards applicable to low-voltage contactors and auxiliary circuits.
It also has international certifications such as UL, CSA, CCC, BV, DNV, RINA, and others depending on the market.
The Schneider Electric TeSys D LC1D18BL 18 A contactor is a solution especially suited to automation panels operating with 24 V DC control circuits. Its 3 NO main contacts, 1 NO + 1 NC auxiliary contacts, low-consumption coil with integrated suppressor, and capability for three-phase motors up to 7.5 kW at 400 V make it ideal for pumps, fans, compressors, machinery, and HVAC systems.