The Schneider Electric LRD05 is a differential thermal overload relay from the TeSys Deca / TeSys LRD range, designed to protect electric motors against overloads, phase loss, and operating conditions that may cause excessive heating. It offers a thermal setting range of 0.63 to 1 A and a trip class 10A, making it an especially suitable solution for use with Schneider Electric TeSys D contactors in motor starters.
Thanks to its adjustable setting, integrated auxiliary contacts, and reset, stop, and test functions, the Schneider LRD05 thermal overload relay allows precise protection to be configured according to the motor’s rated current. It can be mounted directly under compatible LC1D contactors or installed independently on DIN rail or plate using the corresponding specific accessories.
The Schneider Electric LRD05 features a setting range between 0.63 and 1 A. This adjustment allows the relay to be set according to the rated current specified for the motor, providing protection adapted to the actual load characteristics.
During operation, the relay monitors the current flowing to the motor. When a sustained overload occurs above the set level, the thermal mechanism trips and acts on the contactor control circuit, interrupting power to the motor before a prolonged condition can cause damage due to overheating.
The LRD05 is a class 10A relay in accordance with IEC 60947-4-1. This class defines the relay’s time response to overload and makes it suitable for common motor applications whose starting times are compatible with this trip curve.
Schneider Electric specifies a trip threshold for the device of 1.14 ± 0.06 times the setting current Ir, in accordance with IEC 60947-4-1.
In addition to overload protection, the LRD05 is a differential thermal overload relay sensitive to phase loss. This feature is especially important in three-phase motors, since operation with one phase missing can generate severe current imbalance and harmful heating of the windings.
The differential sensitivity allows the relay to respond to this type of fault and help prevent motor damage caused by incomplete or unbalanced supply operation.
The relay integrates two auxiliary contacts, one normally open and one normally closed. These contacts can act on the control circuit when a trip occurs and can be used to stop the contactor and signal the fault condition within the automation or control system.
Feature Value Auxiliary contacts 1 NO + 1 NC Conventional thermal current Ith of the signaling circuit 5 A AC-15 rated current 3 A at 120 V AC DC-13 rated current 0.22 A at 125 V DCThe Schneider LRD05 allows selection between manual reset and automatic reset. In manual mode, after the cause of the overload has been removed, operator intervention is required to restore the relay. In automatic mode, the device can return to operating state once the necessary conditions have been restored.
The reset mode selection allows the relay behavior to be adapted to the safety and operating requirements of each installation.
On the front of the LRD05 are the elements needed to facilitate adjustment and maintenance operations. The unit includes a red stop pushbutton, a blue reset pushbutton, a manual/automatic reset selector, and a test function that simulates a trip to verify correct circuit operation.
It also features a trip indicator that allows the relay status to be visually identified during diagnostic tasks.
The LRD05 thermal overload relay is designed to be installed directly under different Schneider Electric TeSys D contactors. Compatible models include:
This compatibility makes it possible to configure compact contactor and thermal overload relay assemblies for motor control and protection, reducing the space required inside the electrical panel and simplifying wiring.
The Schneider Electric LRD05 can be installed directly under the compatible contactor. It can also be mounted independently on a plate or DIN rail using specific accessories.
For separate installation from the contactor, a compatible terminal block can be used, such as the Schneider Electric LAD7B106 accessory, when the installation configuration requires it.
The power circuit and auxiliary circuit use screw terminals, providing a reliable mechanical connection for industrial electrical panels and automation systems.
According to the manufacturer’s specifications, the power circuit accepts rigid and flexible conductors of different cross-sections depending on the type of termination used. Connections must be made following the tightening torques and conductor sizes indicated in Schneider Electric installation documentation.
The LRD05 is designed to operate in an ambient temperature range of -20 to +60 °C without derating, according to Schneider Electric specifications. The permitted storage temperature ranges from -60 to +70 °C.
Its IP20 protection rating is intended for installation inside electrical panels or enclosures that provide the appropriate degree of protection for the site conditions.
The TeSys Deca LRD05 thermal overload relay is suitable for protecting motors whose rated current falls within the 0.63 to 1 A range. It can be used in control and automation panels for machinery, pumping systems, ventilation, HVAC, conveyors, and other applications using electric motors.
Combined with a TeSys D contactor, it creates a compact motor starter in which the contactor performs the switching operations while the thermal overload relay monitors the motor load conditions.
The Schneider Electric LRD05 complies with IEC 60947-4-1, the standard applicable to low-voltage contactors and motor starters. The range also has multiple international certifications, including IEC, UL, CSA, CCC, EAC, ATEX, and marine application certifications, according to the manufacturer’s documentation.
With its 0.63 to 1 A setting, 10A trip class, phase-loss sensitivity, 1 NO + 1 NC contacts, and direct mounting with TeSys D contactors, the Schneider Electric LRD05 offers a compact and reliable solution for thermal protection of electric motors in professional and industrial installations.